GD-2136H Sisitemu yo gushakisha amakosa
GD2136H Cable Fault sisitemu nigikoresho cyingenzi cyo kubungabunga ubwoko bwose bwinsinga.Ikoresha uburyo butandukanye bwo kumenya kugirango igerageze amakosa ya kabili, ikwiranye ninzego zitandukanye amashanyarazi yumuriro ninsinga zitumanaho.
Sisitemu ikubiyemo ibice bikurikira:
1. GD-2131H Imashanyarazi
2. GD-2132 Umugozi wibeshya
3. GD-2133 Ikizamini cya Cable Ikosa
4. Ibindi bikoresho
GD-2131H Imashanyarazi
Byakoreshejwe kubyara HV impulse mugihe ukoresheje uburyo bwa flashover kugirango umenye amakosa akomeye.
●Ubushobozi bukomeye bwo gutwika, max.umuriro wo gutwika ni 1000W, ingingo yo gusenyuka irashobora gutwikwa mugihe gito kandi kurwanya kwangirika kugabanuka.
●Niba ukorana na GD-2133 Cable Fault Tester, hariho inzira ebyiri zo gushakisha:
a.Umuvuduko muke wa voltage: Niba ukoresheje GD-2133 gusa, uruziga rufunguye hamwe namakosa make ya kaburimbo ya kabili irashobora kuboneka, kandi uburebure bwumugozi burashobora gupimwa cyangwa umuvuduko wumurongo wa kabili urashobora kuboneka.
b.Umuvuduko mwinshi wa flashover: Gusohora impiswi ya voltage yumurongo wikosa ryikitegererezo mugusohora icyuho cyumuzingi, gishobora kumenya intera ikosa.
●Kora impulse yumurongo uhamye.Niba ukorana na GD-2132 Cable Fault Locator, hari imirimo ikurikira:
a.Uburyo bwamajwi bukoreshwa mukuzuza ahantu nyaburanga muri rusange-birwanya-byinshi hamwe na flashover amakosa.
b.Kugirango werekane inzira ya kabili, menya umugozi udasanzwe.
c.Kumenagura ibyuma (hasi yapfuye), ukoresheje ibipimo bya magnetiki-umurima kugirango ubone neza.
●Irashobora kandi gukoreshwa muri DC HV kwihanganira ikizamini.
●Kwinjiza amashanyarazi: AC 220V, 50Hz
●Umuvuduko w'amashanyarazi asohoka: DC 0-32kV (irashobora guhinduka)
●Imbaraga zagereranijwe: 2000VA
●Makeri.energy: 2048J, 4uF
●DC flashover voltage: 32kV
●DC flashover iriho: 63mA
●Max.impulse iriho: 500mA
●Uburyo bwo gusohora: DC HV, igihe kimwe, ukwezi
●Igihe cyo gusohora cycle: amasegonda 3-6
●Ubushyuhe bwibidukikije: 0-40 ℃
●Ubushuhe: <75% RH
●Uburebure: <1000m
●Urwego rwo gukumira: A.
●Igipimo: 430 * 540 * 410mm
●Uburemere: hafi 31kg.
Harimo transmitter, uyakira, Inductive probe, ubwoko bushobora gutahurwaikadiri.Birakwiriye kugerageza ubwoko bwamashanyarazi yose hamwe nuyobora ibyuma.
Igikorwa cyacyo nyamukuru ni ugushakisha ahantu habi, kumenya umuzenguruko naubujyakuzimu bw'insinga z'amashanyarazi.
●Ubukangurambaga bukabije
●Kugabanuka gake
●Ukuri kwukuri
●Kurwanya kwivanga
●LCD ecran kugirango yerekane ibimenyetso n'imiterere
●Yubatswe muri Li-bateri
●Gukurikirana no kumenya intera: umugozi waho 3km, undi mugozi ugera kuri 20km
●Kubona inzitizi zingana: 0-5MΩ.
●Kubona neza: ≤ ± 10cm.
●Ubujyakuzimu bwa kabili: <3m.
Irashobora kugerageza amakosa ya flashover yo hejuru, hejuru-hasiKurwanya guhagarara, imiyoboro ngufi, guhagarika insinga, guhuza nabikubwoko bwose bw'insinga z'amashanyarazi (impamyabumenyi ya voltage 1kV-35kV),umugozi waho, umugozi witumanaho, coaxial-kabili nicyuma cyo hejuru.
Irashobora kandi gupima uburebure bwa kabili n'umuvuduko wo gukwirakwiza umuvuduko w'amashanyarazi kuri kabel.
●Kwipimisha neza, byihuse kandi neza.Ikoresha uburyo bwa LV impulse hamwe na HV flashover detection, igerageza ubwoko bwose bwamakosa.Cyane cyane kuri flashover hamwe namakosa menshi ya inspendance yinsinga, irashobora kugeragezwa muburyo butarinze gutwikwa;niba ifite ibikoresho byo gupima acoustic, umwanya wukuri wikosa urashobora kugenwa neza.
●Gukoresha amakuru yihuse yo gutoranya tekinoroji.Umuvuduko wa A / D ni 100Mhz, kugirango ukemure gusoma igikoresho ni 1m naho agace gahumye ni 1m.
●Ifishi ya Wave hamwe namakuru ahita yerekana kuri ecran nini ya LCD.
●Ifishi ya Wave hamwe nububiko bwa parameter, kwibuka ibikorwa.
●Imikorere yo kugereranya ibizamini bya flake ya kabili hamwe nubusanzwe busanzwe.
●Ifishi yo kwagura ibikorwa.
●Erekana mu buryo butaziguye ikosa n'ikizamini cyo kugereranya intera cyangwa intera igereranije.
●Hindura umuvuduko wo gukwirakwiza umwanya uwariwo wose ukurikije insinga zitandukanye zo kugerageza.
●Yubatswe muri bateri yumuriro.Ingano ntoya, irashobora gutwara.
●Intera yo kugerageza: 15km (Fungura insinga kugeza 100km).
●Kumenya impumyi: 1m
●Umwanzuro: 1m
●Gukoresha ingufu: 5VA
●Ubushyuhe bwibidukikije: 0-40 ℃ (ubushyuhe ntarengwa: -10 ℃ -50 ℃)
●Ubushuhe bugereranije: 40 ℃ (20 ~ 90)% RH
●Umuvuduko w'ikirere: 86-106Kpa
●Ingano: 275 * 220 * 160mm
●Uburemere: 1.8 kg
Ibindi bikoresho birimo AF Stethoscope, Headphones, Grounding Pin, PD Ahantu Rack, RF Tracking Rod.