Sisitemu ya GD-4136H
GD4136H Cable Fault sisitemu nigikoresho cyingenzi cyo kubungabunga ubwoko bwose bwinsinga.Ikoresha uburyo butandukanye bwo kumenya kugirango igerageze amakosa ya kabili, ikwiranye ninzego zitandukanye amashanyarazi yumuriro ninsinga zitumanaho.
Sisitemu ikubiyemo ibice bikurikira:
1.GD-2131H Imashanyarazi
2.GD-4132 Umugozi wibeshya
3.GD-4133 Multi-pulse Cable Ikora Ikosa
4.GD-4133S Multi-pulse Coupler
5.Ibindi bikoresho
GD-2131H Imashanyarazi
Byakoreshejwe kubyara HV impulse mugihe ukoresheje uburyo bwa flashover kugirango umenye amakosa akomeye.
●Ubushobozi bukomeye bwo gutwika, max. gutwika imbaraga ni 1000W, gusenyukaingingo irashobora gutwikwa mugihe gito kandi kurwanya kwangirika kugabanuka.
●Niba ukorana na GD-4133 Cable Ikosa Ikizamini, hariho inzira ebyiri zo gushakisha:
a.Umuvuduko muke wa pulse: Niba ukoresheje GD-4133 gusa, umuzunguruko ufunguye hamwe namakosa make ya kaburimbo ya kabili irashobora kuboneka, kandi uburebure bwumugozi burashobora gupimwa cyangwa umuvuduko wumurongo wa kabili urashobora kuboneka.
b.Umuvuduko mwinshi wa flashover: Gusohora impiswi ya voltage yumurongo wikosa ryikitegererezo mugusohora icyuho cyumuzingi, gishobora kumenya intera ikosa.
●Kora impulse yumurongo uhamye.Niba ukorana na GD-4132 Cable Fault Locator, hari imirimo ikurikira:
a.Inshuro zamajwi: shakisha impedance ndende, flash-over amakosa.
b.Kugirango werekane inzira ya kabili, menya umugozi udasanzwe.
c.Kumenagura ibyuma (hasi yapfuye), ukoresheje ibipimo bya magnetiki-umurima kugirango ubone neza.
●Irashobora kandi gukoreshwa muri DC HV kwihanganira ikizamini.
●Kwinjiza amashanyarazi: AC 220V, 50Hz
●Umuvuduko w'amashanyarazi asohoka: DC 0-32kV (irashobora guhinduka)
●Imbaraga zagereranijwe: 2kVA
●Makeri.energy: 2048J, 4uF
●DC flashover voltage: 32kV
●DC flashover iriho: 63mA
●Max.impulse iriho: 500mA
●Uburyo bwo gusohora: DC HV, igihe kimwe, ukwezi
●Igihe cyo gusohora cycle: amasegonda 3-6
●Ubushyuhe bwibidukikije: 0-40 ℃
●Ubushuhe: <75% RH
●Uburebure: <1000m
●Urwego rwo gukumira: A.
●Igipimo: 430 * 540 * 410mm
●Uburemere: hafi 31kg.
Harimo igice nyamukuru, sensor ya acoustic na magnetiki, anti-urusaku na terefone na charger.
Birakwiye kugerageza ubwoko bwose bwumurongo wamashanyarazi hamwe nuyobora ibyuma.
Igikorwa cyacyo nyamukuru ni ugushakisha ahantu hatari heza, kumenya umuzenguruko n'uburebure bw'insinga z'amashanyarazi.
●Acoustic Magnetic yakira icyarimwe.
●Ubushobozi bukomeye bwo kurwanya kwivanga.
●Hamwe na terefone irwanya urusaku.
●320 * 240 LCD yerekana.
●Yubatswe mubushobozi bunini Li-bateri, hamwe na charger yihuta.
●Ibimenyetso bya Acoustic na Magnetic byerekana ibyerekezo, ibimenyetso n urusaku biroroshye gutandukanya.
●Ukoresheje indanga kugirango upime gutinda kwa acoustic na magnetique, menya neza aho amakosa ari.
●Ukurikije polarite yambere ya magnetic.waveform, irashobora kumenya no kumenya inzira.
1. Kumenya imikorere
a.Ikimenyetso cyo gukwirakwiza ibimenyetso bya Acoustic: umurongo wa 400Hz, umurongo wa 200Hz
b.Inyungu y'ibimenyetso: 80dB
c.Kumenya neza: 0.1m
2.Gutanga ingufu
a.Yubatswe muri Li-batiri, voltage nominal 7.4V, ubushobozi 3000mAH.
b.Gukoresha ingufu: 300mA, guhoraho kumurimo wamasaha 9.
c.Amashanyarazi: kwinjiza AC220V ± 10%, 50Hz.Ibisohoka nominal 8.4V, DC 1A
d.Igihe cyo kwishyuza: Amasaha 4
3. Igipimo: 270mm * 150mm * 210mm
4. Uburemere: 1.5 kg.
5. Koresha imiterere
Ubushyuhe -10 ℃ --40 ℃, ubuhehere 5-90% RH, ubutumburuke <4500m
GD-4133 Ikurikiranwa rya Cable Ikosa rikoreshwa mugupima
intera iri hagati yamakosa.Biroroshye kuri
kora kandi hamwe ninshuti.
Irashobora gukoreshwa wenyine munsi ya voltage ntoya.U.
nder uburyo bwa pulse igezweho, ikeneye gukorana na GD-2131
amashanyarazi menshi. Munsi yuburyo bwinshi bwa pulse, GD-4133S
coupler igomba gukorerwa hamwe.Nyuma yo kumenya intera, GD-4132 ikosora amakosa igomba gukoreshwa mugutandukanya amakosa.Ibicuruzwa birashobora guhurizwa hamwe
urutonde rwibikorwa bihanitse hamwe na sisitemu yo kugerageza ikosa rya sisitemu.
●7inch LCD ya ecran, intera yinshuti.
●Uburyo butandukanye bwo gushakisha intera:
Uburyo buke bwa voltage pulse: burakwiriye gushakisha aho ikosa rito rirwanya, ikosa ryumuzunguruko mugufi, ikosa ryumuzunguruko.Irashobora kandi gukoreshwa mugupima uburebure bwa kabili, guhuza intera, guhuza T, hamwe no guhagarika umugozi.Ubu buryo kandi burashobora gukoreshwa mugukosora umuvuduko wumuraba.
Uburyo bwa pulse bugezweho: Birakwiriye gupima intera yikosa ryinshi ryo guhangana, amakosa yo gusenyuka.Ukoresheje coupler iriho kugirango ukusanye ibimenyetso kuva kwisi, bituma uyikoresha ari kure yumuriro mwinshi.Ubu buryo ni umutekano kandi bwizewe.
Impanuka nyinshi: inzira yambere yo gupima intera.Umuhengeri uroroshye kumenya kandi ukuri ni hejuru.
●200MHz igihe nyacyo cyo gutoranya.Icyiza.0.4m yo gupima.Ifite agace gato kapfuye kandi ni umwihariko wa kabili ngufi kandi hafi ya kabili.
●Kora kuri ecran hanyuma ukande ibikorwa byingenzi
●PIP kopi (pic.ububiko bw'agateganyo)
Hano hazaba idirishya nyamukuru hamwe nububiko butatu bwububiko bwigihe gito bushobora kugenzura imiterere itatu hamwe.
●Sisitemu y'imikorere
Imicungire idasanzwe ya software yo kuzamura software, kugarura no kugarura.
●Igikorwa kinini
Ahantu ho gutangirira, 10 guhuza, ikosa rimwe hamwe nuburebure bwuzuye bushobora gushyirwaho.
Erekana igipimo hamwe no kugerageza imirongo hamwe
●Kubika Waveform no gutumanaho hamwe na mudasobwa.
Ububiko bwimbere bwimiterere.
Hamwe na USB, gukuramo cyangwa kohereza amakuru
Itumanaho na mudasobwa
●Gucunga ingufu
Amatara yinyuma agabanuka niba ntagikorwa muri 2mins hanyuma amashanyarazi muri 10mins niba nta gikorwa.
Yubatswe muri bateri ya Polymer Lithium-ion.
Igihe cyo gukora ni amasaha 5 kuri buri koresha.
Urubanza rukomeye, byoroshye gutwara.
Kubona uburyo | Uburyo buke bwa voltage impulse Hindura uburyo bugezweho Uburyo bwinshi bwo guhumeka niba buhuye na GD-4133S |
Icyiza.Guhitamo inshuro | 200MHz |
Kwunguka | 0-70dB |
Umuvuduko muke wa voltage impulse | 30V |
Igisubizo | 0.4m |
Icyiza.Urutonde | 100km |
Agace kapfuye | 2m |
Batteri | Nickel-metal hydride bateri zishobora kwishyurwa, igihe cyo kwihangana mumasaha 5 |
Imigaragarire y'itumanaho | USB |
Amashanyarazi | Injira AC220V, 50Hz, 2A y'ubu, yishyuza amasaha 8 |
Dim. | 274 × 218 × 81mm |
Ibiro | 3.5kgs |
Gukoresha Ubushyuhe | -10 ℃-40 ℃ |
Ubushuhe | 5-90%RH |
Uburebure | <4500m |
Irimo ikorana na GD-4133 Cable Fault Detector,ikoreshwa mugutahura amakosa menshi yamenetse, amakosa ya flashover,hasi ya impedance yisi no gufungura inzitizi zumurongo wamashanyarazi.
GD-4133S yatanze ibimenyetso byo guhuza pulse ya GD-4133 nakuyitandukanya nibikoresho bya voltage ndende.
●Gukoresha tekinoroji igezweho ya pulse ninshi iringaniye.Imirongo igaragaramo iroroshye kumenya.
●Hamwe n'umutekano HV urinda, umuzenguruko wo gupima hamwe nimbaraga nini za voltage impulse ziherereye mumashanyarazi.
●Gukoresha byoroshye, umutekano kandi wizewe.
●Umuvuduko w'amafaranga: 300V (PP)
●Byemerewe kwinjiza impulse voltage: <35kV
●Byemerewe kwinjiza imbaraga: <2000J
●Amashanyarazi: 220V AC, 50Hz
●Igipimo: 560 * 230 * 220mm
●Uburemere: 7kg.