GD3126A (GD3126B) Ikizamini cyo Kurwanya Kurwanya 5kV / 10TΩ (10kV / 20TΩ)
Ikizamini cya GD3126A (GD3126B) Ikizamini cyo kurwanya insuline gikoreshwa cyane mukubungabunga ibikoresho byamashanyarazi muguhindura insimburangingo, uruganda rwamashanyarazi, nibindi. imiyoboro yameneka (Ix) hamwe nubushobozi bwo kwinjiza (Cx) yubwoko bwose bwibikoresho bya voltage ndende, harimo na switchgear, transformateur, reaction, capacator, moteri, moteri ninsinga, nibindi.
●Yemera microcomputer igenzura, imikorere ya menu na LCD ya ecran ya dot matrix yerekana hamwe nibikorwa bihamye.
●Ubushobozi bukomeye bwo kurwanya-kwivanga, bukwiriye gupimwa mubidukikije bikomeye bya electromagnetic.
●Ubushobozi bunini, burashobora kuzuza ibisabwa bya voltage nini, irwanya imbaraga, ikizamini kinini cyikizamini.
●Hamwe no guhungabana, kutagira ubushuhe hamwe nubutaka butagira umukungugu, ihuze nakazi gakomeye.
●Ukoresha inshuti, garagaza ibisubizo nyabyo hamwe nimpinduka zamakuru.
●Igikorwa cyo kurinda neza, gishobora kwihanganira ingaruka zumuzunguruko mugufi hamwe na capacitance yapimwe ibisigisigi bya voltage.
●5 voltage isohoka intambwe ya 250 V, 500V, 1.0kV, 2.5kV, 5.0kV.
●Umuvuduko wa voltage 6 intambwe ya 250 V, 500V, 1.0kV, 2.5kV, 5.0kV, 10kV.Umuvuduko mwinshi wa buri ntambwe uhora uhindurwa kuva kuri zeru.
●Ibisohoka hejuru ya voltage nayo irashobora guhora ihindurwa.
●Ibipimo byikora bya R15, R60, R600, kubara mu buryo bwikora igipimo cyo kwinjiza, indangagaciro ya polarisiyasi.
●Ikigereranyo ntarengwa cyo gupima ni 0 ~ 10TΩ (0 ~ 20TΩ), uburyo bwo guhinduranya byikora.
●Gupima byikora ubushyuhe bwibidukikije, ubuhehere bwikirere nigihe cyo kugerageza.
●Yerekana igihe cyo gukora ikizamini, inama za buzz kuri buri masegonda 15, iminota 5 idakora izahita ihagarika.
●Mu buryo bwikora gusohora voltage nini nyuma yo gupima birangiye, igihe cyo gusohora ntikirenza amasegonda 30.
●Kubika amatsinda 60 yo gupima ibisubizo, nonvolatility kumyaka 20 ..
●Hamwe na RS232 ya seriveri, ishoboye amakuru kuvugana na mudasobwa.
●Hamwe na printer yo hanze, irashobora gucapa ibipimo byo gupima.(bidashoboka)
●Umuvuduko wa sample yishyuwe werekanwa mbere yo kwipimisha kandi ufite ibimenyetso bifatika.
●Shiraho igihe cyo gukora ikizamini, uhite uhagarika gupima;
●Ushobora kumenya Ix yamenetse Ix hamwe nubushobozi bwa Cx.
Ikigereranyo cyikizamini cya voltage intambwe | GD3126A (5kV) GD3126B (10kV) | ||||||
250V, 500V, 1.0kV, 2.5kV, 5.0kV, 10kV | |||||||
Ibisohoka bya voltage ikosa | ± 5% | ||||||
Urwego rwo kurwanya | Umupaka wo hejuru | 500GΩ~10TΩ | |||||
Umupaka muto | 0.1MΩ | ||||||
Icyiciro cyukuri | Icyiciro 5.0 | ||||||
Ikosa ryinshi ryerekana imbaraga | ± (5% • Ux + 1digital) | ||||||
Kumeneka Ix gupima intera & ikosa | 0.1nA ~ 9.9mA 5% | ||||||
Absorption capacitance Cx gupima intera & ikosa | 0.1pF ~ 99ɥF 5% | ||||||
Ubushyuhe bwo gupima ikosa | ± 0.5 ℃ | ||||||
Ikosa ryo gupima ubushuhe | ± 2% RH | ||||||
Umuyoboro mugufi | <6mA | ||||||
Umuvuduko w'amashanyarazi | <3% | ||||||
Igihe cyo kwipimisha | Kugera ku minota 99 | ||||||
Kurwanya insulation | > 500 MΩ (hagati y'insinga z'ikizamini n'urubanza) | ||||||
Ihangane na voltage | AC10.0kV 50Hz 1min (hagati yinsinga yikizamini nurubanza) | ||||||
Amashanyarazi | Batiri ya litiro | ||||||
Igihe cya serivisi ya Bateri nyuma yo kwishyuza | 30days 10times DAR & 5times PI kumunsi | ||||||
Ubushyuhe bwo gukora nubushuhe | 0 ℃ ~ + 40 ℃ <85% RH | ||||||
Ubushyuhe n'ububiko | - 20 ℃ ~ + 50 ℃ <90% RH | ||||||
Amashanyarazi | 220V AC 50Hz | ||||||
Igipimo (mm) | 325 (L) * 250 (W) * 130 (H) | ||||||
Ibiro | 3.7kg | ||||||
Ikosa ryo gupima ikosa | |||||||
Intambwe ya voltage | 250 V. | 500 V. | 1.0 kV | 2.5 kV | 5.0 kV | 10KV | |
± (3% · Rx + 1d) | 1GΩ | 2GΩ | 4GΩ | 10GΩ | 20GΩ | 40GΩ | |
± (5% · Rx + 1d) | 10GΩ | 20GΩ | 40GΩ | 0.1TΩ | 0.2TΩ | 0.4TΩ | |
± (10% · Rx + 2d) | 100GΩ | 200GΩ | 0.4TΩ | 1TΩ | 2 TΩ | 4TΩ | |
± (25% · Rx + 2d) | 500GΩ | 1TΩ | 2TΩ | 5TΩ | 10TΩ | 20TΩ |
Ikizamini cyo kurwanya insulation | 1 set |
Ikizamini gihuza umugozi wa L terminal (Umutuku) | Imizi 1 (igice 1) |
Ikizamini gihuza umugozi wa G terminal (Icyatsi) | Imizi 1 (igice 1) |
Ikizamini gihuza umugozi wa E terminal (Umukara) | Imizi 1 (igice 1) |
3Apower adapter (Kumashanyarazi itanga amashanyarazi hamwe no kwishyuza ibikoresho) | 1 piece (igice 1) |
RS232 Umurongo w'itumanaho | Imizi 1 (igice 1) |
Umukoresha 'Ubuyobozi | Kopi 1 (igice 1) |
Raporo y'Ikizamini | Kopi 1 (igice 1) |
1. L.
5. Buzzer 6. Ubushyuhe nubushuhe bwa sensor 7. Akabuto ka ESC 8. Akabuto ka UP
9. Itandukaniro knob 10. HANUKA buto 11. OK buto12. Umuvuduko mwinshi uhindura knob
13. Imigaragarire ya RS232 14. Guhindura amashanyarazi15. Kwishyuza sock