GDBR-P Impinduka Yumutwaro Nta-mutwaro hamwe nubushobozi bwo gupima
●Gupima transformateur Nta-mutwaro uhari, Nta gutakaza-umutwaro, umuyagankuba mugufi, gutakaza amashanyarazi magufi n'ubushobozi.
●Uburyo bwo gupima metero eshatu.
●Mugihe ukora ibyiciro bitatu byahinduwe No-umutwaro, umutwaro wikizamini, igikoresho kizasuzuma niba insinga ari nziza mu buryo bwikora, kandi yerekana amashanyarazi atatu yicyiciro, igishushanyo mbonera cya vector.
●Kurangiza ikizamini cyumutwaro munsi ya 1600kVA munsi yo gukwirakwiza transformateur yuzuye kumashini imwe.Kurangiza 2500kVA munsi yikwirakwizwa rya transfert yimitwaro munsi ya 1/3 cyagenwe (Munsi ya 1/3 cyagenwe, igikoresho kirashobora guhindurwa mubintu byatakaye munsi yikigereranyo.)
●Ibisubizo by'ibizamini byose bikosorwa mu buryo bwikora.Igikoresho cyikora gikosora muburyo bukurikira, gukosora imirongo, gukosora ubushyuhe, Gukosora voltage itagabanijwe hamwe no gukosorwa kugezweho.Ibisubizo by'ibizamini birasobanutse neza.
●320 * 240 umucyo mwinshi LCD ecran, hamwe no guhindura urumuri.Gukoraho buto ituma ibikorwa byoroha.
●Isaha-nyayo, gufata itariki yikizamini mu buryo bwikora, ibereye kubika no gucunga ibisubizo byikizamini.
●Byubatswe muburyo bwubwoko bwa printer yumuriro, ibisubizo byihuse byikizamini.
●Kumanura ububiko no gushakisha amakuru (igikoresho cyo kugerageza, ibisubizo byo gupima, igihe cyo kugerageza) imikorere.Ubike ibisubizo bigera kuri 500groups, kohereza amakuru kumurongo kuri PC.
●Emerera intera yagutse kubipimo bya voltage yo hanze na transformateur ya none.Gupima ikintu cyo gupima ibintu byose.
1. Ibizamini
●RMS ya voltage eshatu: Uab, Ubc, Uca.
●Impuzandengo y'agaciro k'ibyiciro bitatu AC voltage: Uab, Ubc, Uca.
●RMS yibyiciro bitatu bigezweho: Ia, Ib, Ic.
●Ijanisha rya No-umutwaro wo gutakaza na No-umutwaro ugezweho: Po, Io%.
●Gutakaza imizigo, ijanisha rya voltage impedance, inzitizi zumuzunguruko mugufi: Pt, ekt, Zt.
●Gutakaza imitwaro, ijanisha rya voltage impedance hamwe ningaruka zumuzunguruko mugihe cy'ubushyuhe ubwo aribwo bwose.
●Guhindura ubushobozi nyabwo hamwe nubushobozi bwaciwe.
2. Ibipimo byingenzi bya tekiniki
●Ibipimo bigezweho: 100mA-60A, ubunyangamugayo: icyiciro 0.2.
●Ikigereranyo cyo gupima amashanyarazi: 10V-650V, ubunyangamugayo: icyiciro 0.2.
●Transformator yo hanze irashobora kwagura igipimo cyibipimo byibikoresho.
●Ibipimo byo gupima inshuro: 40-65Hz, ubunyangamugayo: icyiciro 0.2.
●Imbaraga zinjiza: AC220V ± 10%.
Igice gikuru | 1 pc |
Umugozi w'amashanyarazi | 1 pc |
Umugozi wo kugerageza | 1 set |
Umugozi udasanzwe wumuzingi | 1 pc |
Imfashanyigisho y'abakoresha | 1 pc |
Raporo y'ibizamini by'uruganda | 1 pc |