Sisitemu ya GDCF-900T Yashizweho na Cable Ikosa Sisitemu
Sisitemu Yashizwe Kumurongo Wibikoresho Byakoreshejwe muburyo bwa Cable Ikosora (gutwika), Mbere-Ahantu, Inzira, Inzira-Kugaragaza & Kugerageza insinga za HV & LV zubwoko butandukanye & ubunini.Gushiraho birakwiriye gukora ibikorwa byinshi byavuzwe haruguru kumurongo wamashanyarazi wurwego rutandukanye rwa voltage cyane cyane 33KV, 11KV, 415V hamwe ninsinga zo kugenzura hamwe na 1.1 KV.Igice kizakoreshwa muburyo bwa kabili aribwo XLPE, PVC, PILC hamwe nuyobora Al / Cu.Intsinga zashyizwe munsi yubutaka (munsi yubutaka busanzwe, imyobo, cyangwa hejuru ya RCC, Gucukura Horizontal mumiyoboro ya HDD), hejuru yubutaka cyangwa igice munsi & igice hejuru yubutaka hamwe nuburebure bwa kabili hafi ya 25Km.
Inzira ya kabili ikwiranye no gushakisha amakosa no kwerekana ubwoko bukurikira bwamakosa.
●Kurwanya cyane
●Kurwanya bike
●Ubwoko bwigihe gito bwerekana amakosa.
●Ahantu habi
●Sisitemu ikoresha impiswi nyinshi (uburyo bwo kwerekana ARC), inshuro eshatu impiswi, uburyo bwa impulse, uburyo bwa flashover, uburyo bwa TDR kugirango bukore ibipimo bikabije byubwoko bwose bwamakosa.
●Ikoresha uburyo bwa magnetique acoustic kugirango ibone neza ingingo zamakosa.
●Ikoresha ihame rya electromagnetic induction kugirango ikurikirane umugozi utazwi no kumenya ubujyakuzimu bwa kabili.
●Menya kandi utobore insinga za bunch.
●Shakisha kandi upime umugozi.
Imodoka yashizwemo na sisitemu yo gupima ikosa ikoresha igishushanyo mbonera kandi cyubumuntu kugirango hamenyekane amakosa yingenzi ya insinga z'amashanyarazi ya 33KV, 11KV na 415V, kumenya aho ikosa ryakorewe hanze, aho ryagenwe neza, ikizamini cyinzira, kumenyekanisha ubuzima, gutobora umutekano , DC irwanya ubwoko bwose bwibikoresho byipimisha, ibikoresho byo gukwirakwiza ingufu, ibikoresho nibikoresho byingirakamaro bisabwa bishyirwa kumodoka yihariye yahinduwe.
Igikorwa cyose cyikizamini gifite umutekano kandi gifunze, kandi imikorere yikizamini iratandukanye kandi ibisubizo byikizamini nibyo.
●Imodoka igizwe nibice bitatu: cab, icyumba cyo gukoreramo hamwe nicyumba cyibikoresho.
●Imiterere ya konsole ikora irumvikana, kandi ikizamini cyo kubika insinga, guca imanza zumutungo, no gupima intera ikabije irashobora kurangizwa rwose mumodoka.
●Ikizamini cyikizamini gishobora kurangiza gupima hafi ya kabili ya point point intera kandi irashobora guhita ifunga umwanya.
●Icyumba cyo kugenzura cyateguwe hamwe nimbaraga zigenga zifite imbaraga nyinshi zifite ingufu nyinshi, LCD yerekana igihe nyacyo cyumuvuduko na voltage, muburyo bwubwenge bwuzuye bwuzuye amashanyarazi menshi no gusohora.
●Kumenyekanisha umugozi, inzira yikizamini cyashyizwe mubyumba byo gukoreramo.
●Imbonerahamwe yimikorere ikozwe muri epoxy resin kugirango byose bibe byiza kandi byiza.Igikoresho gikurura ibikoresho cyakozwe mugukora ibyuma no gufunga amajwi ya gari ya moshi.Biraramba, ntibinyerera, birinda kwambara kandi byoroshye kubisuzuma.Iremeza umutekano wibikorwa byo kwipimisha.
Imiterere y'imbere
1 —— Ahantu ho gutwara
2 —— Ahantu ho gukorera
3 —— Igice cyo kugenzura ikigo
4 —— Gutunganya ibimenyetso bitari byo
5 —— Ibizamini by'ibizamini by'ibinyabiziga
6—— Igice kinini cyo gupima
7 —— Igice cyo gukingira
8 —— Generator
9—— Umuyoboro mwinshi wa kabili reel
10 —— Umugozi wubutaka
11 —— Urukuta rwo kwigunga
Sisitemu yose irimo
Ingingo | Izina | Icyitegererezo No. | Qty |
1 | Vehicle | ------------- | 1 |
2 | Multi-pulse umugozi wikizamini | GD-4133 | 1 |
3 | Impanuka
| GD-4133S
| 1 |
4 | CIkosa
| GD-4132
| 1 |
5 | High voltage impulse generator | GD-2131H
| 1 |
6 | CIkiranga | GD-2134D
| 1 |
7 | Cigikoresho gishobora gutobora | GD-2135B | 1 |
GD-2131H Imashanyarazi
Byakoreshejwe kubyara HV impulse mugihe ukoresheje uburyo bwa flashover kugirango umenye amakosa akomeye.
●Ubushobozi bukomeye bwo gutwika, max.imbaraga zo gutwika ni 1000W, ingingo yo gusenyuka irashobora gutwikwa mugihe gito kandi kurwanya kwangirika kugabanuka.
●Niba ukorana na GD-4133 Cable Ikosa Ikizamini, hariho inzira ebyiri zo gushakisha:
a.Umuvuduko muke wa pulse: Niba ukoresheje GD-4133 gusa, uruziga rufunguye hamwe nudukosa duto duto twa kabili dushobora kuboneka, kandi uburebure bwumugozi burashobora gupimwa, cyangwa umuvuduko wumurongo wa kabili urashobora kuboneka.
b.Umuvuduko mwinshi wa flashover: Gusohora impiswi ya voltage yumurongo wikosa ryikitegererezo mugusohora icyuho cyumuzingi, gishobora kumenya intera ikosa.
●Kora impulse yumurongo uhamye.Niba ukorana na GD-4132 Cable Fault Locator, hari imirimo ikurikira:
a.Inshuro zamajwi: shakisha impedance yo hejuru, flash-over amakosa.
b.Kugirango werekane inzira ya kabili, menya umugozi udasanzwe.
c.Kumenagura ibyuma (hasi yapfuye), ukoresheje ibipimo bya magnetiki-umurima kugirango ubone neza.
●Irashobora kandi gukoreshwa muri DC HV kwihanganira ikizamini.
●Kwinjiza amashanyarazi: AC 220V, 50Hz
●Umuvuduko w'amashanyarazi asohoka: DC 0-32kV (irashobora guhinduka)
●Imbaraga zagereranijwe: 2kVA
●Icyiza.ingufu: 2048J, 4uF
●DC flashover voltage: 32kV
●DC flashover iriho: 63mA
●Icyiza.impulse igezweho: 500mA
●Uburyo bwo gusohora: DC HV, igihe kimwe, ukwezi
●Igihe cyo gusohora cycle: amasegonda 3-6
●Ubushyuhe bwibidukikije: 0-40 ℃
●Ubushuhe: <75% RH
●Uburebure: <1000m
●Urwego rwo gukumira: A.
●Igipimo: 430 * 540 * 410mm
●Uburemere: hafi 31kg.
GD-4132 Umugozi wibeshya
Harimo igice nyamukuru, sensor ya acoustic na magnetiki, anti-urusaku na terefone na charger.Birakwiye kugerageza ubwoko bwose bwumurongo wamashanyarazi hamwe nuyobora ibyuma.Igikorwa cyacyo nyamukuru ni ugushakisha ahantu hatari heza, kumenya umuzenguruko n'uburebure bw'insinga z'amashanyarazi.
●Acoustic Magnetic yakira icyarimwe
●Ubushobozi bukomeye bwo kurwanya kwivanga
●Hamwe na terefone irwanya urusaku.
●320 * 240 LCD yerekanaYubatswe mubushobozi bunini Li-bateri, hamwe na charger yihuta.
●Ibimenyetso bya Acoustic na Magnetic byerekana ibyerekezo, ibimenyetso n urusaku biroroshye gutandukanya.
●Ukoresheje indanga kugirango upime gutinda kwa acoustic na magnetique, menya neza aho amakosa ari.Ukurikije polarite yambere ya magnetiki yumurongo, irashobora kumenya no kumenya inzira.
1. Kumenya imikorere
a.Ikimenyetso cyo gukwirakwiza ibimenyetso bya Acoustic: umurongo wa 400Hz, umurongo wa 200Hz
b.Inyungu y'ibimenyetso: 80dB
c.Kumenya neza: 0.1m
2. Amashanyarazi a.Yubatswe muri Li-batiri, voltage nominal 7.4V, ubushobozi 3000mAH.b.Gukoresha ingufu: 300mA, guhoraho kumurimo wamasaha 9.c.Amashanyarazi: kwinjizaAC220V ± 10%, 50Hz.Ibisohoka ku izina 8.4V, DC 1A d.Igihe cyo kwishyuza: Amasaha 4
3. Igipimo: 270mm * 150mm * 210mm
4. Uburemere: 1.5 kg.
5. Koresha imiterere Ubushyuhe -10 ℃ --40 ℃, ubuhehere 5-90% RH, ubutumburuke <4500m
GD-4133 Umugozi wamashanyarazi
GD-4133 Cable Fault Detectot ikoreshwa mugupima intera iri hagati yamakosa.Biroroshye gukora kandi hamwe ninshuti.
Irashobora gukoreshwa wenyine munsi ya voltage ntoya.Muburyo bwimikorere ya pulse, ikeneye gukorana na generator ya GD-2131.Muburyo bwinshi bwa pulse, GD-4133S coupler igomba gukorerwa hamwe.Nyuma yo kumenya intera, GD-4132 ikosora amakosa igomba gukoreshwa mugutandukanya amakosa.Ibicuruzwa birashobora guhurizwa hamwe murwego rwo hejuru rwo gukora hamwe na sisitemu yo kugerageza amakosa ya kabili.
●7inch LCD ya ecran, intera yinshuti.
●Uburyo butandukanye bwo gushakisha intera:
Uburyo buke bwa voltage pulse: burakwiriye gushakisha aho ikosa rito rirwanya, ikosa ryumuzunguruko mugufi, ikosa ryumuzunguruko.Irashobora kandi gukoreshwa mugupima uburebure bwa kabili, guhuza intera, guhuza T, hamwe no guhagarika umugozi.Ubu buryo kandi burashobora gukoreshwa mugukosora umuvuduko wumuraba.
Uburyo bwa pulse bugezweho: Birakwiriye gupima intera yikosa ryinshi ryo guhangana, amakosa yo gusenyuka.Ukoresheje coupler iriho kugirango ukusanye ibimenyetso kuva kwisi, bituma uyikoresha ari kure yumuriro mwinshi.Ubu buryo ni umutekano kandi bwizewe.
Impanuka nyinshi: inzira yambere yo gupima intera.Umuhengeri uroroshye kumenya kandi ukuri ni hejuru.
●200MHz igihe nyacyo cyo gutoranya.Icyiza.0.4m yo gupima.Ifite agace gato kapfuye kandi ni umwihariko wa kabili ngufi kandi hafi ya kabili.
●Kora kuri ecran hanyuma ukande ibikorwa byingenzi
●Kopi ya PIP (ifoto yo kubika by'agateganyo)
●Hano hazaba idirishya nyamukuru hamwe nububiko butatu bwububiko bwigihe gito bushobora kugenzura imiterere itatu hamwe.
●Sisitemu y'imikorere
Imicungire idasanzwe ya software yo kuzamura software, kugarura no kugarura.
●Igikorwa kinini
Ahantu ho gutangirira, 10 guhuza, ikosa rimwe hamwe nuburebure bwuzuye bushobora gushyirwaho.
Erekana igipimo hamwe no kugerageza imirongo hamwe
●Kubika Waveform no gutumanaho hamwe na mudasobwa.
Ububiko bwimbere bwimiterere.
Hamwe na USB, gukuramo cyangwa kohereza amakuru
Itumanaho na mudasobwa
●Gucunga ingufu
Amatara yinyuma agabanuka niba ntagikorwa muri 2mins hanyuma amashanyarazi muri 10mins niba nta gikorwa.
Yubatswe muri bateri ya Polymer Lithium-ion.
Igihe cyo gukora ni amasaha 5 kuri buri koresha.
Urubanza rukomeye, byoroshye gutwara.
Kubona uburyo | Uburyo buke bwa voltage impulse Hindura uburyo bugezweho Uburyo bwinshi bwo guhumeka niba buhuye na GD-4133S |
Icyiza.Guhitamo inshuro | 200MHz |
Kwunguka | 0-70dB |
Umuvuduko muke wa voltage impulse | 30V |
Icyiza.imyanzuro | 0.4m |
Icyiza.Urutonde | 100km |
Agace kapfuye | 2m |
Batteri | Nickel-metal hydride bateri zishobora kwishyurwa, igihe cyo kwihangana mumasaha 5 |
Imigaragarire y'itumanaho | USB |
Amashanyarazi | Injira AC220V, 50Hz, 2A y'ubu, yishyuza amasaha 8 |
Dim. | 274 × 218 × 81mm |
Ibiro | 3.5kgs |
Gukoresha Ubushyuhe | -10℃-40℃ |
Ubushuhe | 5-90% RH |
Uburebure | <4500m |
GD-4133S Coupler nyinshi
Irimo ikorana na GD-4133 Cable Fault Detector, ikoreshwa mugutahura amakosa menshi yamenetse, amakosa ya flashover, isi idahwitse hamwe nuruzitiro rwumuzunguruko rwinsinga z'amashanyarazi.GD-4133S yatanze ibimenyetso byo guhuza pulse ya GD-4133 no kuyitandukanya nibikoresho bya voltage nyinshi.
●Gukoresha tekinoroji ya tekinoroji ya Multiplepulseandpulsebalance.Ihinduka ryumurongo ryoroshye biroroshye kumenya.
●Hamwe n'umutekano HV urinda, umuzenguruko wo gupima hamwe nimbaraga nini za voltage impulse ziherereye mumashanyarazi.
●Gukoresha byoroshye, umutekano kandi wizewe.
Ibisobanuro
●Umuvuduko w'amafaranga: 300V (PP)
●Byemerewe kwinjiza impulse voltage: <35kV
●Byemerewe kwinjiza imbaraga: <2000J
●Imbaraga zinjiza: 220VAC, 50Hz
●Igipimo: 560 * 230 * 220mm
●Uburemere: 7kg.
GD-2134D Ikimenyetso Cyerekana
GD-2134D Cable Identifier ikubiyemo transmitter hamwe niyakira, irashobora gukoreshwa mugushakisha ibimenyetso hamwe nubujyakuzimu bwinsinga zubutaka hamwe nu miyoboro yicyuma, kugirango tumenye umugozi uva mumigozi myinshi.
●Erekana mu buryo butaziguye aho umuyoboro uherereye.
●Ibumoso / Iburyo bwiburyo bwerekana Cable Route Tracing.
●Igihe nyacyo gipima imiyoboro yicyerekezo hamwe nibinyoma / gukosora byihuse munsi yigihe gito.
●Ikosora / Ibinyoma.Bizerekana imbere mugihe umugozi wamenyekanye ukurikiranwa neza.Bitabaye ibyo, izerekana inyuma kandi izerekana "?".
●Gupima byikora byimbitse nubu.
●Kumenyekanisha insinga: Kumenyekanisha Clamp no kumenyekanisha stethoscope.Kumenyekanisha clamp birashobora gupima amplitude hamwe nicyerekezo cya kabili neza kandi bigatanga ibisubizo nyabyo.Kumenyekanisha Stethoscope nuburyo gakondo mugihe bitoroshye gukoresha Clamp iranga.Nibyoroshye insinga zo kumenya Stethoscope.
●Gukoresha Rack (ibikoresho bidahwitse) kugirango umenye aho ikosa ryakorewe.Ntabwo ari ngombwa kumenyera umwanya wa zeru.Umwambi werekana icyerekezo cyamakosa.
●Byuzuye muburyo bwa digitifike yuzuye itondekanya kandi itunganyirizwa hamwe, hamwe no kwakirwa kwagutse no kwivanga gukomeye.Ihagarika byimazeyo ingufu zumurongo hamwe no guhuza ibikorwa bivuye hafi yinsinga zikoresha.
●Kumenya neza no gutahura neza.
●Yubatswe mubushobozi bunini bwa batiri ya Litiyumu.Automatic power-off iyo munsi ya voltage cyangwa ntagikorwa cyigihe kinini.
Ikwirakwiza
●Ibisohoka (Uburyo butatu): Ibisohokayandikiro bitaziguye, Clamp Coupling isohoka (kubihitamo), Imirasire.
●Inshuro (6 yo guhitamo): 640Hz, 1280Hz, 10kHz, 33kHz, 83kHz, harimo 640Hz na 1280Hz ni inshuro zikomeye.Irashobora gutahura imikorere yo Gukosora / Kubeshya no kwerekana imiyoboro hamwe nubufasha bwa Receiver.
●Ibimenyetso byerekana amakosa kugirango umenye amakosa ya pipe.
●Amashanyarazi asohoka: Mak.10W, 10 intambwe zishobora guhinduka.
●Ibisohoka bisohoka muburyo butaziguye: Max.150Vpp.
●Automatic impedance ihuza hamwe nibikorwa byo kurenza & kurinda-bigufi.
●Amashanyarazi: Bateri ya Lithium yimbere yimbere, 4pcs, moderi no.18650.nominal 7.4V, 6.8Ah.
●Birakomeye kandi byoroshye.
Uwakiriye
●Uburyo bwinjiza: bwubatswe mukwakira coil, kwakira clamp (kubishaka), echometero (kubishaka), Rack (kubishaka).
●Ibice bibiri byerekana pasiporo: imirongo yumurongo na radio (RF).Ntibikenewe ko uhuza amajwi yerekana amajwi.
●Kwakira inshuro:
Inshuro igaragara neza: 640Hz, 1280Hz, 10kHz, 33kHz, 83kHz
PF yerekana inshuro nyinshi: 50 / 60Hz na 250 / 300Hz (ukoresha iboneza)
RF passive detection frequency: centre frequency ni 10kHz, 33kHz, 83kHz.
●Uburyo bwo gutahura: uburyo bwo hejuru, uburyo bugufi, uburyo bwubusa.
●320 * 240 pigiseli LCD ya ecran.
●Yubatswe muri batiri ya lithium isubirwamo, 2pcs 18650 Li bateri, nominal.7.4V, 3.4Ah.
●Birakomeye kandi byoroshye.
Ibindi bisobanuro
●Ingano: transformateur 270 * 220 * 85mm, yakira 700 * 270 * 120mm.
●Uburemere: kohereza 2.2kg, uwakira 2.2kg.
●Amashanyarazi: kwinjiza AC 100-240V, 50 / 60Hz, ibisohoka DC 8.4V, 2A.
●Imiterere y'akazi: Ubushyuhe -10--40 ℃.Ubushuhe 5-90% RH, Uburebure <4500m.
GD-2135 Igikoresho Cyuma Cyuma
GD-2135B Igikoresho Cyuma Cyuma Cyuma nacyo kiranga umugozi, kugirango umenye umugozi uva mumigozi.
Nibikoresho bidahuza umutekano byacumita, hamwe no kugenzura kure.
Iki gikoresho kirimo ibice bibiri, igikoresho cyo gutera imisumari hamwe nigikoresho cyo kugenzura.Ikoreshwa na bateri, itandukanya igikoresho cyacumuye na sisitemu y'amashanyarazi, kugirango umutekano utange amashanyarazi.
●Birakwiriye gutobora ubwoko bwose bw'insinga z'amashanyarazi, umutekano kandi wizewe.
●Uburyo bubiri bwo gukora, burimo kure nigihe.Utubuto tubiri two gukoreshwa kugirango twinjire muburyo bwakazi, menya umutekano wumukoresha.
●Utubuto tubiri kure (urufunguzo C na D kanda icyarimwe).Kugirango wakire neza, antenne yohereza ya kure igomba gukururwa rwose.
●Gukoresha imbunda ebyiri kugirango utobore impande ebyiri.Igikorwa kimwe cyo kugerageza kurangiza inshuro ebyiri.
●Hamwe no gutabaza amajwi na LCD yerekana.
●Igishushanyo kinini cyo gukingirwa nubukanishi na elegitoroniki.
●Umwihariko wagenewe gucumita insinga, ushyizwe kumurongo, ushyizwe kumpande zose.
●Gukoresha bateri ikoreshwa, ikwiriye gukoreshwa mwishyamba idafite amashanyarazi.Na none, itandukanya igikoresho cyo gutobora muri sisitemu yingufu, kugirango umutekano ubeho.
●Intera ya kure idafite insinga: ≤ 20M.
●Umugozi usaba: insinga zose z'amashanyarazi ≤ ¢ 125mm
●Imbaraga zakazi: 6pcs 1.5V.
●Imiterere yakazi: ubushyuhe -10--50 ℃, ubuhehereRH <95%.
●Uburemere: 15kg harimo na aluminium.
●Igipimo: 48 * 45 * 16cm