GDPDS-341 SF6 Isesengura ry'amashanyarazi ya Leta isesengura rusange
Kugeza ubu, urwego rwa voltage ya UHV rwa 110KV no hejuru rukoresha SF6 ya gaze ya gaze ya GIS ifunze GIS nkibikoresho byingenzi byibanze bya sitasiyo, isuzuma ryimiterere yimbere ya GIS igerwaho ahanini nuburyo bwo gutahura igice hamwe nuburyo bwo gusesengura imiti ya SF6 murugo no mu mahanga.Iyo gusohora igice bibaye mugihe cyambere cyo kwangirika kwimbere muri GIS, bizatera umutekano muke kubikorwa byacyo.Uburyo bwo gutahura igice gisohoka ahanini burimo uburyo butatu: ikizamini cyo gusohora igice cya ultra-high frequency igice, ikizamini cyo gusohora ultrasonic igice, hamwe no kumenya imiti ya gaz ya SF6.Kugeza ubu, hari ibikoresho bitandukanye kuri ubu bwoko bwuburyo bwikizamini ku isoko.Kumwanya wa GIS gusohora igice kizima, abatekinisiye babiri babigize umwuga mumashanyarazi na chimie basabwa gutwara ibikoresho byinshi icyarimwe kugirango basohore igice kimwe na gaze ya gaze ya SF6, byoroshye kandi mugihe gikennye cyane.Urebye uko ibintu bimeze muri iki gihe cyo gutahura igice muri GIS, isosiyete ya HV HIPOT yashyizeho ikoranabuhanga mpuzamahanga ryateye imbere mu guteza imbere isesengura rusange ry’amashanyarazi ya SF6.Gukomatanya uburyo bwa UHF, uburyo bwa ultrasonic hamwe nisesengura rya gaze ya SF6 mubikoresho bimwe birashobora kunoza uburyo bwo gutahura nuburyo bwo guca imanza zatewe no gusohora igice mubikoresho bya GIS, kandi bikanoza ukuri kwicyemezo cyo gusohora igice, bitanga ubufasha bwizewe bwa tekiniki yo gufata icyemezo.
Usibye igice cyo gusesengura gazi ya SF6, isesengura rya leta rya SF6 ryisesengura ryuzuye kandi rihuza tekinoroji yo gutahura igice.Abakoresha barashobora gukoresha ibikoresho byo gutahura igice kugirango bakore ibizamini byambere byo gusohora no kugenzura ibikoresho byamashanyarazi byapimwe.Ibikoresho by'amashanyarazi bimaze kugaragara ko bikekwa ko byananiranye gusohora igice, igice cyo gusesengura gaze ya SF6 kirashobora gukoreshwa ako kanya mugukora gaze ya gaze ya SF6, isesengura ryumubiri n’imiti.Imiterere yimiterere yikintu cyapimwe irashobora kugenwa no kubaza ibipimo ngenderwaho byigihugu binyuze mubisubizo byisesengura ryumubiri nubumara.Mugihe kimwe, isesengura rya gaze ya SF6 hamwe nikizamini cyo gusohora igice gishobora gukorwa icyarimwe.Mugushushanya amakuru yubunini bwumubiri nubunini bwa chimique, turashobora kumenya neza neza imiterere yimiterere nimpamvu yibikoresho byamashanyarazi.
Inyungu nyamukuru yubushakashatsi bwamashanyarazi ya SF6 isesengura ni uko ishobora kumenya byimazeyo imiterere yimikorere yibikoresho byamashanyarazi binyuze mubisubizo bibiri byo gusohora igice hamwe na gaze ya gaz ya SF6 nisesengura ryumubiri, kandi irashobora kumenya imikorere yibikoresho byamashanyarazi byihuse kandi neza.Irashobora kandi gukoreshwa nkibikoresho byoroshye byo kwipimisha kugirango bipimishe ahabigenewe micro-amazi ya gaze ya SF6, ubuziranenge, nibicuruzwa byangirika.
●Gusohora igice hamwe nisesengura ryubushuhe bwumucyo, ubuziranenge nibicuruzwa byibikoresho bya gaze ya gaz ya SF6 kumashanyarazi.
●Ikizamini cya gazi ya SF6.
●Ikizamini cyiza cya gaze ya SF6 yo kugarura no gukoresha.
●Gukora gaze nziza.
●Inganda zikoresha inganda zitanga gaze yumye.
●Gukoresha ubushakashatsi niterambere.
●Gusukura icyumba / kugenzura inzu yumye.
●Ahantu ho gutunganya ubushyuhe hamwe na laboratoire ya gazi yerekana ubuhehere, nkumwuka, CO2, N2, H2, O2, SF6, He, Ar nizindi myuka ya inert.
●Porogaramu isesengura igice cyo gusesengura ishingiye kuri ARM yashyizwemo, kwerekana software ishingiye kuri sisitemu ya Windows.
●Sisitemu ya software isuzuma ingufu zisohoka n’ahantu hakurikijwe amakuru yamenyekanye, kandi irashobora kwerekana ikarita ya PRPS na PRPD, igishushanyo cya ellipse, ikarita yerekana igipimo, ikarita ya QT, amakarita ya NT, amakarita ya PRPD, amakarita cum-QN ya buri muyoboro w’ibimenyetso, kandi irashobora kwerekana PD signal amplitude na pulse numero ya buri kimenyetso.Kandi amakuru yose arashobora kubikwa mugihe nyacyo.
●Ikusanyamakuru ryakira rishobora icyarimwe gushiraho imiyoboro 4 yuburyo bumwe cyangwa butandukanye, kandi irashobora icyarimwe gukusanya no gusesengura imiyoboro 4 yibimenyetso.
●Kwiyubaka-byihuse byihuta byikitegererezo, imiyoboro 4-yoguhuza amakuru, gutunganya ibimenyetso, gukuramo ibimenyetso biranga, amakuru arashobora koherezwa kumurongo wintoki ukoresheje insinga na simsiz.
●Ibyuma byose byatumijwe mu mahanga bifite ibyuma bisobanutse neza hamwe na gahunda yo kwiyemeza gukora byerekana neza ko amakuru yo kumenya ibicu, ubuziranenge n’ibicuruzwa byangirika bihamye kandi byizewe umwaka wose.
●Inzira ya gazi yose hamwe nibikoresho bya polymer bihanitse, byemeza ko nta nkuta zamazi zimanikwa kandi byemeza umuvuduko wikizamini.
●Amavuta adafite amavuta adafite ibyuma-bigenga valve ikoreshwa kugirango hamenyekane neza agaciro gapimwe.
●Porogaramu igezweho ya algorithms itezimbere ikizamini cyukuri.
●Gutangira birashobora kumenyekana, nta nzira ihindagurika, guhindura ubushyuhe no gukosora amakuru.
●Imbaraga za batiri ya lithium ikomeye, menya AC na DC amashanyarazi abiri.Nta mbaraga za AC zisabwa.Amashanyarazi ya Litiyumu akomeje gukora amasaha arenga 8 adakeneye amashanyarazi yo hanze.
●Kurwanya anti-electromagnetic intervention interineti kugirango igenzure ibicuruzwa byizewe.
●Ikizamini gihamye, igipimo cyikime gisanzwe nigiciro cyahinduwe cyikime kuri 20 ℃ birashobora gutangwa mugihe kimwe.
●Ibipimo byo gupima ubuziranenge ni 0.5% byurwego rwose, rushobora gukoreshwa mugupima gaze ya gaze ya SF6 hamwe na 70% birimo gaze ya SF6.
●Ikibanza cyiza cyo kugerageza cyerekana, uyikoresha arashobora guhindura byihuse gazi, kugabanya igihe cyibizamini.
●Inlet yakozwe hamwe na micro yo gufunga hamwe, inzira ya gaze yapimwe ntizatemba mugihe inzira ya gaze ihagaritswe.
●Umuyoboro wogupima ibyuma bya Swagelok bidafite ibyuma bikoreshwa mukuzunguruka gaze ya gaze, byongerera igihe cyo gukora ibikoresho.
Igice cyo gutahura igice:
Ikimenyetso cya PD | |
CPU Inshuro | 1.2GHz |
Sisitemu y'imikorere | Linx yashyizwemo sisitemu y'imikorere |
Umuyoboro wicyuma | Umuyoboro wa LAN |
Umuyoboro udafite insinga | Yubatswe muri WiFi idafite umugozi |
Sisitemu ikoresha ububiko | 512M |
Ububiko bwa sisitemu | 256M |
Inshuro yo gushaka amakuru | 250MHz |
Umuyoboro wa Ultrasonic | |
Urwego rwo gupima | AE: 0-10mV; AA: 0-100dBuV |
Urutonde rwo kumenya inshuro | 20 ~ 200kHz |
Umuyoboro wa UHF | |
Inshuro | 300 ~ 1800MHz |
Urwego rwo gupima | -80 ~ 0dBm |
Ikosa | ± 1dBm |
Icyemezo | 1dBm |
Umuyoboro wa HFCT | |
Ikirangantego | 0.5 ~ 100MHz |
Ikosa | ± 1dB |
Ibyiyumvo | 15mV / 1mA |
Urwego rudasanzwe | 60dB |
Urwego rwo gupima | 0-1000mV |
Ukuri | 1dB |
Umuyoboro wa TEV | |
Ikirangantego | 3 ~ 100MHz |
Urwego rwo gupima | 0-60dBmV |
Ibyiyumvo | 0.01mV |
Ikosa | ± 1dBmV |
Icyemezo | 1dBmV |
Batteri | |
Bateri yubatswe | Batiri ya Litiyumu, 12V,6000mAh |
Koresha igihe | hafi10amasaha |
Igihe cyo kwishyuza | Ibyerekeye4amasaha |
Kurinda Bateri | Kurenza-voltage no kurinda birenze |
Amashanyarazier | |
Ikigereranyo cya voltage | 12.6V |
Kwishyuza ibyasohotse | 2A |
Ubushyuhe bwo gukora | -20 ℃ -60 ℃ |
Gukoresha ubuhehere | <80% |
Kwerekana amakuru no gusesengura | |
Porogaramu ikwiranye na terefone iyo ari yo yose hamwe na sisitemu ya Windows, kandi abayikoresha barashobora kuyihitamo bonyine. | |
Ibidukikije | |
Ubushyuhe bwo gukora | -20 ℃ ~ 50 ℃ |
Ubushuhe bwibidukikije | 0 ~ 90% RH |
Urwego rwa IP | 54 |
Igice cyo gusesengura gaze ya SF6
Ubushuhe bwa SF6
●Uburyo bwo gupima: Ihame ryo gupima rirwanya kandi rifite ubushobozi
●Urwego rwo gupima: ikime -80 ℃ - + 20 ℃ (inkunga ppmv)
●Ukuri: ± 1 ℃
(iyo ubushyuhe bwikime buri munsi ya 0 ℃, ibyasohotse bya sensor nubukonje)
●Igihe cyo gusubiza: 63% [90%]
+ 20 → -20 ℃ Td 5s [45s]
-20 → -60 ℃ Td 10s [240s]
●Icyemezo: 0.01 ℃
●Gusubiramo: ± 0.5 ℃
●Igice cyo kwerekana: ℃, ppm, ℃ P20 (agaciro kahinduwe kuri 20 ℃)
SF6
●Uburyo bwo gupima: Ihame ryo gupima Infrared (sensor ya NDIR)
●Urwego rwo gupima: 0 ~ 100% SF6
●Igihe cyo gusubiza: [90%] 60s
●Ukuri: ± 0.5% FS
●Gusubiramo: ± 0.5%
●Icyemezo: 0.01%
●Igice cyerekana:%
SF6 Ibicuruzwa byangirika
●Uburyo bwo gupima: Ihame ry'ibipimo by'amashanyarazi (ibyuma bikoresha amashanyarazi)
●Urwego rwo gupima: H2S: 0 ~ 100ppmv
SO2: 0 ~ 100ppmv
CO: 0 ~ 500ppmv
HF: 0 ~ 50ppmv
●Icyemezo: 0.5ppmv
●Igice cyo kwerekana: ppmv
Gazi itemba
●Ibipimo by'ikime: SF6 hamwe na gaze: 400-600ml / min
SF6 gupima ubuziranenge: 300-450ml / min
SF6 Ibicuruzwa byangirika: 250-300ml / min
●Kugaragaza neza: 0-1000mL metero yimibare
●Icyitegererezo cya gaze: ≤1MPa
●Kurinda Sensor: Ibyuma bitagira umuyonga
●Amashanyarazi: 110-220VAC ± 10%, 50Hz, gukoresha AC / DC, kurinda amafaranga arenze, gukora ubudahwema ntabwo biri munsi yisaha 8.
●Koresha ubushyuhe bwibidukikije: -20 - + 60 ℃
●Ibidukikije bikora: ubushyuhe: -35 - 70 ℃
Umuvuduko: 0 - 20bar
Icyitegererezo cya gazi itemba: nta-ngaruka
●Ubushuhe: 90% RH
●Igipimo: 570 * 418 * 320mm
●Uburemere: hafi 18 kg.
Ikizamini gikuru | Igice 1 |
UHF sensor | Igice 1 |
Ultrasonic sensor | Igice 1 |
Rukuruzi rwa TEV | Igice 1 |
HFCT | Igice 1 |
Umugozi wibimenyetso | Igice 1 |
Abahuza | 1 set |
Umuyoboro wa Teflon (ushizemo valve ihindura flux na connexion yihuta) | 1 set |
Umuyoboro murizo | 1 set |
Ibice by'ibicuruzwa | 1 set |
Amashanyarazi | Igice 1 |
Agatabo gafasha abakoresha | Igice 1 |
Raporo y'Ikizamini | Igice 1 |