GDPQ-5000 Isesengura ryiza ryimbaraga
GDPQ-5000 Isesengura ryimbaraga zimbaraga nigikoresho cyuzuye cyipimisha cyateguwe neza nisosiyete yacu kandi cyagenewe umwihariko wo gupima umurima wibyiciro bitatu, byinshi-bikora kandi byubwenge, imikorere yumuntu-mashini.Biroroshye gukoresha, ecran nini ya LCD yerekana, imiterere ihanitse, intera haba mubushinwa nicyongereza, imiterere-shitingi yububiko nibindi.Irashobora icyarimwe gupima imiyoboro 4-imiyoboro (ABC icyiciro cya gatatu nicyuma kidafite aho kibogamiye), umuyoboro wa 4-umuyoboro (ABC ibice bitatu byumubyigano hamwe numurongo utabogamye wumurongo wubutaka), agaciro kamashanyarazi yumuriro wa voltage, ntarengwa / agaciro ntarengwa mugihe runaka , ibyiciro bitatu byo kutaringaniza ibintu, igihe gito cya voltage flicker, transformateur K ibintu, imbaraga zikora, imbaraga zidasanzwe, imbaraga zigaragara, imbaraga nimbaraga zo kwimura ibintu, imbaraga zikora, imbaraga zidasanzwe, imbaraga zigaragara, kugoreka guhuza hamwe no guhuza, nibindi;Erekana igihe nyacyo cyo guhinduranya, guhuza ibipimo byerekana imbonerahamwe ya voltage ya none;Gufata mu buryo bwihuse impinduka zihuse za voltage, kugenzura gutangira, kugenzura ibipimo byimbaraga no gutanga urutonde rwimpuruza, kubyara imbonerahamwe yerekana igihe kirekire cyamakuru yipimishije.
GDPQ-5000 Isesengura ryiza ryimbaraga zemeza DSP + ARM yububiko bubiri, DSP ikoreshwa mugukusanya amakuru no gutunganya algorithm, ARM ikoreshwa kuri protocole y'itumanaho no gutunganya imashini ya mashini;Kugereranya ibimenyetso bisa nibice 2 AD7655 ya sosiyete ya ADI.Icyemezo cya AD7655 ni 16 bit kandi ni 4 umuyoboro uhuza icyitegererezo.Igipimo kinini cyo gutoranya gishobora kugera kuri 1 MSPS, kugirango hamenyekane neza niba umuyoboro wukuri hamwe nubusugire bwamakuru, kandi ntushobora kubura impinduka zigihe gito muri gride, birashobora kuba ukuri kugirango umenye imiterere yinzibacyuho izamuka kandi igabanuka cyane, kandi ihindagurika ryihuse ako kanya. ;DSP ikora inshuro zirenga 200 MHZ, kugirango ibashe gukurikirana mugihe cyogukoresha amashanyarazi kandi ihindure byimazeyo icyitegererezo kugirango tumenye guhuza ingufu zumurongo hamwe ninshuro zicyitegererezo;Ukoresheje 5.6 -kuri LCD yerekana ibara ryerekana, imyanzuro ya 640 utudomo x 480 utudomo, hamwe nibitandukaniro bitandukanye byerekana amabara hagati yibipimo byicyiciro, imiterere ya flake, igishushanyo mbonera, igipimo gihuza, uyikoresha arashobora gukora neza kandi akumva neza leta ya power grid ibipimo.Byubatswe muri flash yibuka irashobora kubika itsinda 60 rya ecran ya ecran icyarimwe, amatsinda 150 yo gufata voltage transient / igishusho cyumuvuduko, hamwe nitsinda 12800 ryurutonde.Gutangira icyitegererezo cyerekana ubudahwema gufata uburyo bwo gutangira imiyoboro ya 100 s.Yubatswe muri 2G ikarita yububiko kugirango ubike ibyerekezo byerekana umurongo, icyarimwe gufata amajwi 20 ibipimo (ushobora guhitamo ukurikije ibikenewe) gukusanya amakuru rimwe mumasegonda atanu, inyandiko yerekana umurongo irashobora kubikwa muminsi 300.
Yitwa kandi Intelligent Three Phase Power Quality Analyser, Multifunctional Power Quality Analyser, icyarimwe hamwe nibikorwa byisesengura bihuza, metero volt-ampere metero,ibipimo by'amashanyarazi.Irakoreshwa mu nganda z'amashanyarazi, peteroli, metallurgie, gari ya moshi, inganda zicukura amabuye y'agaciro, ikigo cy'ubushakashatsi mu bumenyi, ishami rya metrologiya.Cyane cyane gikwiye gusesengura byuzuye no gusuzuma kuri voltage zose, ikigezweho, imbaraga, imbaraga, guhuza, ibice byamashanyarazi.
2.1.Igikorwa cyo gupima
●Waveform nyayo-yerekana (imiyoboro 4 voltage / imiyoboro 4 igezweho).
●Nukuri RMS indangagaciro za voltage ningendo.
●Ibigize DC ya voltage.
●Impinga zigezweho na voltage agaciro.
●Ntarengwa kandi ntarengwa igice cyizenguruka RMS igezweho na voltage agaciro.
●Igishushanyo cya Phasor.
●Gupima buri guhuza kugeza kuri 50.
●Imbonerahamwe yumurongo yerekana ibipimo bihuza byubu na voltage ya buri cyiciro.
●Kugoreka guhuza byose (THD).
●Imbaraga, reaction, imbaraga zigaragara, kubice no guhuriza hamwe.
●Imbaraga, zikora, imbaraga zigaragara, kubice no guhuriza hamwe.
●Impinduka K.
●Ibintu byingufu (PF) nibintu byimurwa (DPF cyangwa COSΦ).
●Umuvuduko w'igihe gito wa flicker (PST).
●Ibice bitatu kutaringaniza (ikigezweho na voltage).
2.2.Igikorwa cyo gufata igihe gito
Gukurikirana ihinduka ryihuse rya power grid voltage ibipimo byerekana, harimo ihindagurika ryumubyigano wa voltage, umuvuduko wamashanyarazi wihuta, sag hamwe nigihe gito cyo guhagarika, guhagarika ingufu zigihe gito, ingaruka zumuvuduko nubu hamwe na voltage igoreka ako kanya.Ibikoresho birashobora kubika ibice 150 byigihe gito.
2.3.Gutangira gukurikirana
Gukurikirana ibintu byiyongera kumurongo hamwe no gutangira mugihe ibikoresho byamashanyarazi bitangiye, fasha mugushushanya neza ubushobozi.Urashobora kwerekana RMS izamuka / igabanuka kumurongo Mugikorwa cyo gutangira, ibahasha umurongo wamabahasha yo gutangira, umurongo wumuyoboro wimiyoboro 4 numuyoboro wa voltage 4.Kwandika hafi 100s nyuma ya trigger, kubika ububiko / voltage ako kanya hamwe nu murongo uhindagurika wa buri cyiciro muri 100.
2.4.Imirongo yerekana imbonerahamwe yo gufata no kubika imikorere
Bika ibipimo byose byikizamini cyibikorwa byibanze (Urms, Uthd, Ucf, Uunb, Hz, Vrms, Vthd, Vcf, Vunb, PST, Intwaro, Athd, Acf, Aunb, KF, W, VAR, VA, PF, COSφ, TANφ), 50 ya voltage ihuza, 50 ihuza ubu.Kandi ushireho inzira igenda.Andika amakuru igihe kirekire ukurikije ibikenewe (guhitamo icyarimwe ibipimo 20 kugirango wandike amakuru rimwe mumasegonda atanu, urashobora kwandika iminsi 300.)
2.5.Imikorere yo kumenyesha
Shiraho imipaka ntarengwa ukurikije ibikenewe, ukurikirane indangagaciro niba zirenze, niba isasu rizabyara impuruza, nka: voltage, ikigezweho, kutaringaniza, igipimo gihuza, inshuro, imbaraga zikora, kugoreka ibintu byose.Urashobora gushiraho impuruza 40 zitandukanye, buri tsinda rishobora gushyiraho ibipimo bitandukanye byo gukurikirana (harimo 50 bihuza, byose hamwe 123 ibipimo bitandukanye) kandi bigabanya agaciro, nabyo birashobora gushiraho igihe gito cyo kugenzura.Igiti gishobora kubamo impuruza zigera ku 12.800.
2.6.Igikorwa cyo gufata amashusho
Isura iyo ariyo yose irashobora gukizwa (ecran ya ecran), mugihe kimwe ihita yandika igihe nuburyo bwikizamini.Nkibishobora kubika voltage nuburyo bugezweho, imbonerahamwe yumurongo, igishushanyo cya fasornibindi birashobora kubika ntarengwa 60 ya ecran ya ecran.
2.7.Igikorwa cyo gutumanaho
Ganira na mudasobwa ukoresheje USB, Porogaramu ikurikirana irashobora kwerekana imiterere yuburyo bwo gusesengura ubuziranenge bwimbaraga, soma ibyerekezo byigihe gito, ibishushanyo mbonera byerekana amajwi, ibimenyetso byerekana ibimenyetso, amashusho, hamwe no kwerekana kuri mudasobwa.
2.8.Gushiraho imikorere
Umukoresha arashobora kugena igihe nitariki, iboneza rya ecran itandukanye kandi ikayangana, ibisobanuro bya buri cyiciro cyo gutandukanya amabara.
Guhitamo ubwoko bwihuza kumurongo.
Iboneza ryubwoko bwa sensor igezweho hamwe na voltage ratios.
2.9.Ubufasha
Buri cyiciro cyibikorwa gishobora gukanda urufunguzo "ubufasha" kugirango ubone amakuru afatika.
3.1.Imiterere shingiro n'imikorere
cImpamvu | Ikizamini | Imiterere shingiro | Imiterere y'akazi |
Ubushyuhe bwibidukikije | Ibipimo byose | (23 ± 2) ° C. | -10 ° C ~ 40 ° C. |
Ubushuhe bugereranije | Ibipimo byose | 40% ~ 60% | <80% |
Icyiciro-kuri-kidafite aho kibogamiye | Ibipimo byose | (100 ± 1%) V. | 1.0V ~ 1000V |
Icyiciro-Kuri-icyiciro cya voltage | Nukuri RMS icyiciro-kuri-icyiciro cya voltage | (200 ± 1%) V. | 1.0V ~ 2000V |
Ibiriho | Ikigezweho cya RMS | (5 ± 1%) A. | 10mA ~ 10A |
Umuyoboro | Ibipimo byose | 50Hz ± 0.1Hz | 40Hz ~ 70Hz |
Guhindura icyiciro | Imbaraga zikora nimbaraga zikora | Cosφ = 1 | Cosφ: 0.2 ~ 1.0 |
Imbaraga zifatika nimbaraga zidasanzwe | Sinφ = 1 | Icyaha: 0.2 ~ 1.0 | |
Harmonic | Ibipimo byose | <0.1% | 0.0% ~ 100% |
Umuvuduko ukabije w'amashanyarazi | Ibipimo byose | <10% | 0.0% ~ 100% |
Umuvuduko wakazi wibikoresho | Ibipimo byose | DC9.8V ± 0.1V | DC9.5V ~ 10.5V |
Umuriro w'amashanyarazi wo hanze, Umwanya wa rukuruzi | Ibipimo byose | Tugomba kwirinda | |
Umwanya wikizamini | Ibipimo bifitanye isano nibigezweho | Umugozi wapimwe hagati ya clamp. |
3.2.Ibisobanuro rusange
Amashanyarazi | Amashanyarazi ya lithium-ion yamashanyarazi ipakira 9.6V, charger yamashanyarazi. |
Ikimenyetso cya Batiri | Ikimenyetso cya bateri yerekana ingufu zijugunywa.Iyo voltage iri hasi cyane, guhagarika byikora nyuma yiminota 1. |
Gukoresha ingufu | Kugeza ubu gukoresha ikizamini gisanzwe 490 mA, guhora ukora amasaha 8. |
Uburyo bwo kwerekana | LCD ibara rya ecran, 640dots × 480dots, santimetero 5,6, kwerekana indangarubuga: 116mm × 88mm. |
Ingano ya clamp | 008B clamp ntoya ityaye: 7.5mm × 13mm; |
Ibipimo by'ibikoresho | L × W × H: 240mm × 170mm × 68 mm. |
Umubare w'imiyoboro | 4U / 4I. |
Icyiciro -cyiciro cya voltage | 1.0V ~ 2000V. |
Icyiciro-kuri-kidafite aho kibogamiye | 1.0V ~ 1000V. |
Ibiriho | 008B clamp y'ubu: 10mA ~ 10.0A; |
Inshuro | 40Hz ~ 70Hz. |
Ibipimo by'amashanyarazi | W, VA, Var, PF, DPF, cosφ, tanφ. |
Ibipimo byingufu | Ninde, Varh, Vah. |
Harmonic | Tegeka 0 ~ 50. |
Kugoreka kwuzuye | Tegeka 0 ~ 50, buri cyiciro. |
Uburyo bw'impuguke | Yego. |
Umubare wibyanditswe byinzibacyuho | Amaseti 150. |
Umuvuduko w'amashanyarazi | Yego. |
Gutangira uburyo bwubu | Nibyo, amasegonda 100. |
Ibyiciro 3 kutaringaniza | Yego. |
Andika | Iminsi 300 (icyarimwe gufata amajwi 20, andika ingingo imwe buri masegonda 5). |
Min / Max yanditse agaciro | Gupima agaciro ntarengwa kandi ntarengwa mugihe runaka. |
Imenyesha | Ubwoko 40 butandukanye bwibintu byatoranijwe, 12.800 bishyiraho ibiti byo gutabaza. |
Impinga | Yego. |
Igishushanyo cya Phasor | Mu buryo bwikora. |
Ubushobozi bwa snapshots | 60. |
Ururimi | Icyongereza |
Itumanaho | USB. |
Kuzimya mu buryo bwikora | Iyo ubukangurambaga bwo gutabaza bwatangijwe cyangwa gushakisha abimura, gufata inrush iriho, cyangwa gufata amajwi birategereje cyangwa biri gukorwa, igikoresho ntabwo kizimya. |
Mubundi buryo bwo kugerageza, iminota 15 idafite urufunguzo, guhagarika byikora nyuma yiminota 1. | |
Imikorere yinyuma | Nibyo, bikwiriye gukoreshwa nijoro n'ahantu hijimye. |
Ibiro | Nyiricyubahiro: 1.6kg (hamwe na bateri). |
008B clamp ntoya ityaye: 170g × 4; | |
Uburebure bwa voltage test | 3m. |
Uburebure bwa sensor ya none | 2m. |
Ubushyuhe bwo gukoran'ubushuhe | -10 ° C ~ 40 ° C;munsi ya 80% Rh. |
Ubushyuhe n'ububiko | -10 ° C ~ 60 ° C;munsi ya 70% Rh. |
Kwinjiza inzitizi | Kwinjiza inzitizi ya voltage yikizamini: 1MΩ. |
Ihangane na voltage | Ihangane 3700V / 50Hz ya sinusoidal AC voltage kumunota 1 hagati yo gukoresha ibikoresho nigikonoshwa. |
Kwikingira | Hagati yo gukoresha ibikoresho nigikonoshwa ≥10MΩ. |
Imiterere | Kwikuba kabiri, hamwe na insulasiyo yinyeganyeza-sheath. |
Amategeko atekanye | IEC 61010 1000V Injangwe III / 600V CAT IV, IEC61010-031, IEC61326, Impamyabumenyi y’umwanda: 2. |
3.3.Igikoresho gisobanutse neza (ukuyemo sensor iriho)
Wiyubashye kumenyekanisha amakuru akurikira (ku shingiro ryimiterere shingiro hamwe na sensor nziza igezweho, umurongo utunganijwe neza, nta guhinduranya icyiciro).
Igipimo | Urwego | Erekana imyanzuro | Ikosa ntarengwa murwego rwoherejwe |
Inshuro | 40Hz ~ 70Hz | 0.01Hz | ± (0.03) Hz |
Nukuri RMS icyiciro-kuri-kidafite aho kibogamiye | 1.0V ~ 1000V | Icyemezo gito 0.1V | ± (0.5% + 5dgt) |
Nukuri RMS icyiciro -cyiciro cya voltage | 1.0V ~ 2000V | Icyemezo gito 0.1V | ± (0.5% + 5dgt) |
Umuyoboro wa DC | 1.0V ~ 1000V | Icyemezo gito 0.1V | ± (1.0% + 5dgt) |
Ikigezweho cya RMS | 10mA ~ 10A | Icyemezo gito 1mA | ± (0.5% + 5dgt) |
Impinga ya fase-kuri-idafite aho ibogamiye | 1.0V ~ 1414V | Icyemezo gito 0.1V | ± (1.0% + 5dgt) |
Impinga ya voltage-icyiciro | 1.0V ~ 2828V | Icyemezo gito 0.1V | ± (1.0% + 5dgt) |
Impinga ya none | 10mA ~ 10A | Icyemezo gito 1mA | ± (1.0% + 5dgt) |
Impamvu yo hejuru | 1.00 ~ 3.99 | 0.01 | ± (1% + 2dgt) |
4.00 ~ 9.99 | 0.01 | ± (5% + 2dgt) | |
Imbaraga zifatika | 0.000W ~ 9.999kW | Icyemezo gito 0.001W | ± (1% + 3dgt) Cosφ≥0.8 |
± (1.5% + 10dgt) 0.2≤Cosφ <0.8 | |||
Imbaraga zifatika, inductive cyangwa capacitive | 0.000VAR ~ 9.999kVAR | Icyemezo gito 0.001VAR | ± (1% + 3dgt) Icyaha0.5 |
± (1.5% + 10dgt) 0.2≤Sinφ <0.5 | |||
Imbaraga zigaragara | 0.000VA ~ 9.999kVA | Icyemezo gito 0.001VA | ± (1% + 3dgt) |
Impamvu zingufu | -1.000 ~ 1.000 | 0.001 | ± (1.5% + 3dgt) Cosφ≥0.5 |
± (1.5% + 10dgt) 0.2≤Cosφ <0.5 | |||
Ingufu zifatika | 0.000Wh ~ 9999.9MWh | Icyemezo gito 0.001Wh | ± (1% + 3dgt) Cosφ≥0.8 |
± (1.5% + 10dgt) 0.2≤Cosφ <0.8 | |||
Ingufu zifatika, inductive cyangwa capacitive | 0.000VARh ~ 9999.9MVARh | Icyemezo gito 0.001VARh | ± (1% + 3dgt) Icyaha0.5 |
± (1.5% + 10dgt) 0.2≤Sinφ <0.5 | |||
Ingufu zidasanzwe | 0.000VAh ~ 9999.9MVAh | Icyemezo gito 0.001VAh | ± (1% + 3dgt) |
Inguni y'icyiciro | -179 ° ~ 180 ° | 1 ° | ± (2 °) |
Tanφ (VA≥50VA) | -32.76 ~ 32.76 | Icyemezo gito 0.001 | : ± (1 °) |
Guhinduranya icyiciro cyibintu (DPF) | -1.000 ~ 1.000 | 0.001 | : ± (1 °) |
Ikigereranyo cya Harmonic (gutumiza 1 kugeza 50)(Vrms> 50V) | 0.0% ~ 99.9% | 0.1% | ± (1% + 5dgt) |
Inguni ihuza (Vrms> 50V) | -179 ° ~ 180 ° | 1 ° | ± (3 °) guhuza gahunda 1 kugeza 25 |
± (10 °) guhuza gahunda 26 kugeza 50 | |||
Ubwuzuzanye Ikigereranyo (THD cyangwa THD-F) ≤50 | 0.0% ~ 99.9% | 0.1% | ± (1% + 5dgt) |
Impamvu yo kugoreka (DF cyangwa THD-R) ≤50 | 0.0% ~ 99.9% | 0.1% | ± (1% + 10dgt) |
Impinduka K. | 1.00 ~ 99.99 | 0.01 | ± (5%) |
Ibyiciro 3 kutaringaniza | 0.0% ~ 100% | 0.1% | ± (1%) |
3.4.Imiterere ya sensor ya none
Ubwoko bwa sensor ya none | Ikigezweho cya RMS | Ikosa ryinshi ryukuri rya RMS | Ikosa ryinshi ryicyiciro φ |
008B clamp y'ubu | 10mA ~ 99mA | ± (1% + 3dgt) | ± (1.5 °), Intwaro≥20mA |
100mA ~ 10.0A | ± (1% + 3dgt) | ± (1 °) | |
040B clamp | 0.10A ~ 0.99A | ± (1% + 3dgt) | ± (1.5°) |
1.00A ~ 100A | ± (1% + 3dgt) | ± (1 °) | |
068B clamp | 1.0A ~ 9.9A | ± (2% + 3dgt) | ± (3°) |
10.0A ~ 1000A | ± (2% + 3dgt) | ± (2°) | |
300Fclamp y'ubu | 10A ~ 99A | ± (1% + 3dgt) | ± (3°) |
100A ~ 3000A | ± (1% + 3dgt) | ± (2°) |
Icyitonderwa: clamp n'ibikoresho bigomba guhuzwa bihuye, ntibishobora kwinjizwa bitandukanye.
4.1.Iboneza bisanzwe
Oya. | Kugenwa | Umubare |
1 | Igikoresho. | 1 |
2 | Umufuka wibikoresho. | 1 |
3 | Rukuruzi. | 12 (Ubwoko 3) |
4 | Kugerageza insinga. | 5 (umuhondo, icyatsi, umutuku, ubururu, umukara) |
5 | Amashusho y'ingona. | 5 |
6 | Ikizamini. | 5 |
7 | Imbaraga zidasanzwe. | 1 |
8 | Umugozi wamatariki ya USB. | 1 |
9 | CD ya software. | 1 |
10 | Ibikoresho bya batiri ya Litiyumu. | 1 (Yubatswe mubikoresho) |
11 | Ububiko bwa 2GB. | 1 (Shira mu gikoresho) |
12 | Igitabo, ikarita ya garanti, icyemezo. | 1 |
4.2.Ibiro
Oya. | Kugenwa | Ibiro |
1 | Igikoresho. | 1.6Kg (hamwe na batiri). |
2 | 008B clamp ntoya ityaye. | 170g*4. |
3 | 040B kuzengurukaclamp y'ubu. | 185g *4 |
4 | 068B kuzengurukaclamp y'ubu. | 530g *4 |
5 | 300FUmuyoboro woroshyeclamp(hamwe numubare). | 330g *4 |
6 | Igerageza insinga hamwe na adapt. | 900g. |