GDCL-10kA Impulse Yubu
●Ubushyuhe bwibidukikije: -10 ℃ kugeza 40 ℃
●Ubushuhe bujyanye: ≤ 85% RH
●Uburebure: m 1000m
●Gukoresha mu nzu
●Nta mukungugu utwara, nta muriro cyangwa akaga gashobora guturika, nta byuma byangirika cyangwa gaze.
●Imbaraga za voltage waveform ni sine wave, igipimo cyo kugoreka <5%
●Kurwanya isi ntabwo birenze 1Ω.
IEC60099-4: 2014 Abata muri yombi Abaganga-Igice cya 4: Abafata ibyuma-oxyde bafata nta cyuho cya sisitemu ya ac.
GB311.1-1997 Guhuza ibikorwa byo gukwirakwiza amashanyarazi ya HV no guhinduka.
IEC 60060-1 Tekinike Yipimisha Yumuvuduko mwinshi- Ibisabwa muri rusange.
IEC 60060-2 Tekinike Yipimishije Yumuvuduko- Sisitemu yo gupima.
GB / T16896.1-1997 Ibyuma bifata amajwi ya Digitale Yumubyigano mwinshi.
DLT992-2006 Gushyira mu bikorwa Amategeko yo gupima Impulse ya Voltage.
DL / T613-1997 Ibisobanuro bya tekiniki kubitumizwa muri AC bidafite icyuma gifata ibyuma.
Ukoresheje imirongo ya LC na RL, capacitor yishyurwa C isohora mumitwaro idafite umurongo urwanya inductance L hamwe na R irwanya R kubyara ingufu zihuye nibisabwa bisanzwe.

●Imiterere ya none: 8 / 20μs
●Ikigereranyo kigezweho: 10kA
●Uburyo bwa Ignition: Pneumatic displacement isohora umupira intera.Igenzura ryikora, kugenzura intoki.
●Ubu polarite ya none: nziza.Umuhengeri werekana: ibibi-bibi;ibisigisigi bya voltage-nziza.
●Ibipimo bigezweho: Igiceri cya Rogowski (0-50kA), ubunyangamugayo: 1%.
●Ibipimo bya voltage isigaye: kugabanya voltage igabanya (0-100kV), ubunyangamugayo: 1%
●Muri rusange ibipimo byo gupima: 3%
●Kwerekana Waveform: Oscilloscope (Tektronix) na PC.
●Oscilloscope na capacitor yishyuza voltage yashyizwe kuri PC nurufunguzo rumwe.
●Kubika amakuru: kuri PC.Ibipimo byo gupima hamwe na flimform byegeranijwe na oscilloscope, hanyuma ihita yoherezwa kuri PC ikoresheje icyambu cya USB, hanyuma ikabikwa nka format ya Excel mububiko bwateganijwe kuri disiki ikomeye ya mudasobwa.
●Kurinda umutekano: birenze-voltage, birenze-bigezweho, guhuza kugenzura guhuza, guhagarara byihutirwa, guhagarara byikora.Bifite ibikoresho byo kumanura intoki: abakozi babakozi bagomba gusohora hamwe nubutaka mbere yo kuvugana numubiri wa generator, gusimbuza imashini itanga imbaraga, gusimbuza ikintu cyipimisha, gusana, nibindi, hanyuma bagahuza umurongo wubutaka na HV kumpera yumubiri.
●Kurwanya impamvu: ≤1Ω
●Amashanyarazi: 220V ± 10%, 50Hz;ubushobozi 10kVA
Igice cyo kwishyuza
1) Uburyo bwo kwishyuza: igice cya kabiri cyo gukosora hamwe nigihe gihoraho mumuzunguruko wa LC kuruhande rwibanze.Uruhande rwibanze rufite imiyoboro-ngufi / kurenza-imitwaro irinda.
2) Umuvuduko mwinshi wa rectifier diode: reba voltage 150kV, Max.Impuzandengo ya 0.2A.
3) Transformer yibanze ya voltage 220V, voltage ya kabiri 50kV, ubushobozi bwapimwe 10kVA.
4.
5.
6) Igenzura rya voltage ya capacitor: DC irwanya voltage igabanya ikoresha ikirahure cya uranium hamwe nicyuma cya firime.Ikimenyetso cya voltage yikiganza gito cya voltage cyoherezwa muri sisitemu yo gupima na kabili ikingiwe.
Igice cyo gusohora
1.
2) Igikoresho cyo gusohora gikoresha pneumatic solenoid valve itandukanya hamwe nuburyo bwo hasi, bufite imiterere ihamye, ihererekanyabubasha rikomeye nigikorwa cyizewe.
3) Umwanya wo gusohora bikozwe muri grafite hamwe nubushyuhe bukomeye kandi birwanya umuyaga munini.

Amashanyarazi
1) Ububiko bune bubika ingufu bugabanijwemo amatsinda abiri hanyuma bugashyirwa kumurongo wa chassis.Induction ya Wave-imbere hamwe no kurwanya imiraba-iherezo byashyizwe mumwanya uhuye, byoroshye, bisobanutse, bihamye kandi byizewe.
2) Gufata igikoresho cyibizamini bikomezwa na pneumatic pusher.
3) Igikoresho cyo gutwika gikoresha pneumatike kugirango yimure intera yumupira yitaruye kandi isohore mu cyuho cyumupira, gihamye kandi cyizewe.
1) Umuvuduko usigaye: kugabanya imbaraga za voltage igabanya, kutarwanya inductive, precision high, Max.voltage ni 30kV, ifite 1pc 75Ω umugozi wo gupima, metero 5.
2) Ibiriho: Ukoresheje igiceri cya Rogowski hamwe numuyoboro ntarengwa wa 100kA na 1pc 75Ω umugozi wo gupima, metero 5.
3) Oscilloscope: Ukoresheje Tektronix DPO2002B, igipimo cya sample ya 1GS / s, umurongo mugari wa 100MHz, imiyoboro ibiri.
4) Porogaramu: ifite ibikoresho bya ICG impulse ya sisitemu yo gupima, hamwe namakuru hamwe numurongo wo gusoma / kubika no kubara.
Igice cyo kugenzura
1) Ubwoko bwimbonerahamwe Workbench ituma abakozi bakora bakora bicaye, byoroshye.
2) Inama y'Abaminisitiri ifite ibyuma byimukanwa hamwe n’inkunga ihamye, ishobora koroshya kugenda no kugena imyanya.
3) Igishushanyo cyiza cya sisitemu yo kugenzura, interineti yorohereza abakoresha, buto 3 gusa (kwishyuza, gusohora, gutwika) hamwe na bande ihinduranya (guhinduranya imirongo ine), kwizerwa cyane, imiterere yoroshye, byoroshye gukora, byoroshye kubungabunga.
4) Igenamiterere rya Oscilloscope rigenzurwa na mudasobwa kandi ryuzuzwa nurufunguzo rumwe, rwirinda imikorere yintoki igoye (oscilloscope ifite imirimo myinshi, bigoye kubatari abanyamwuga kugenzura).
5) Capacitor yishyuza voltage igenzurwa na mudasobwa, hamwe ninteruro isobanutse nibikorwa byoroshye.
6) Oscilloscope ishyiraho itumanaho hamwe na mudasobwa, amakuru yo gupima hamwe na flimform ihita ibikwa muri mudasobwa, kandi inyandiko ya Excel ihita ikorwa.
7) Amashanyarazi yo kugenzura sisitemu: yitandukanije na transformateur na filteri.
8) Kurinda: birenze-voltage, birenze-bigezweho, guhuza kugenzura guhuza, guhagarara byihutirwa, guhagarara byikora, nibindi.
Porogaramu yisesengura yateguwe kugirango impulse igeragezwa irashobora guhita isoma imiterere yamakuru hamwe namakuru binyuze mu itumanaho na oscilloscope no gusuzuma imiterere yumurongo ukurikije uburyo bwo gupima ibipimo bya IEC1083-2.Impinga ya none, voltage peak, umwanya-wimbere nigihe cyigihe cyo kurangira bibarwa mu buryo bwikora kandi bikerekanwa kuri ecran ya mudasobwa hamwe na test ya flake.
Ibyatanzwe hamwe na flake irashobora kubikwa mu buryo bwikora kandi ubudahwema (kurasa bidasanzwe kurubuga rwibizamini)