Muri Kanama, abatekinisiye nyuma yo kugurisha HV Hipot bagiye i Xiangyang.Icyari kigamijwe muri uru rugendo kwari ugutanga serivisi zogukoresha amashanyarazi ya Xiangyang.
Nyuma yo kugera kurubuga, hamwe nubufasha nubufatanye bwabakiriya, hazashyirwaho amashanyarazi ya voltage yumuriro wa voltage.
Kumwanya wo gukuramo GDCY-400kV yumurabyo impulse ya generator
Kurubuga rwumupira intera intera: kalibrasi yumupira wumubiri hamwe na chopper ball intera (3000/200 / yapimwe)
Kurubuga rwiruka-mukizamini: 30KV nziza kandi mbi polarite ibizamini byinshi (hura T1 = 1.2 ± 30% / T2 = 50 ± 20% us / TC = 2 kugeza 6us)
Ikizamini cyimbaraga kurubuga: igipimo cya voltage 80% gisohoka
Kurubuga rwamahugurwa nibikorwa:
Imyitozo y'abakiriya - igeragezwa ryibicuruzwa byapimwe: 10KV ihindura imbaraga
1. Ikizamini cyuzuye
Ibisabwa byikizamini: voltage yikizamini 75KV, igihe cyo guhinduranya T1 = 1.2 ± 30% / T2 = 50 ± 20% twe
Igikorwa cyo murwego: ukoresheje ibyiciro bibiri bya voltage ibisohoka
Kurubuga rwa modulisiyo:
Kurwanya umutwe wumutwe: 150Ω kurwego rwa mbere, 500Ω kurwego rwa kabiri (2 1KΩ murwego rumwe)
Kurwanya umurizo wumurongo: icyiciro cya 1 45Ω, icyiciro cya 2 45Ω
Imikorere yikizamini hamwe na flake:
Ikizamini cya Cutoff
Ibisabwa byikizamini: voltage yikizamini 85KV, umwanya wumutwe T1 = 1.2 ± 30%, igihe cyo guhagarika TC = 2 kugeza 6us
Igikorwa cyo murwego: ukoresheje ibyiciro bibiri bya voltage ibisohoka
Kurubuga rwa modulisiyo:
Kurwanya umutwe wumuraba: Urwego 1 75Ω, Urwego 2 500Ω (2 1KΩ murwego rumwe)
Kurwanya umurizo wumurongo: icyiciro cya 1 45Ω, icyiciro cya 2 45Ω
Imikorere yikizamini hamwe na flake:
Nyuma yuruhererekane rwamahugurwa, umukiriya afite ubushishozi bwimbitse bwibikoresho byose, bigatuma umukiriya arushaho kwigirira ikizere mubikorwa nyirizina!
Igihe cyo kohereza: Kanama-24-2022