Amavuta yagaruwe adasukuwe yitwa amavuta yo hasi, arimo amazi menshi n’umwanda, kandi imbaraga za dielectric ziri munsi ya 12KV.Cyane cyane kumavuta yo mu rwego rwo hasi hamwe namazi menshi, abayikoresha bamwe bakoresha ibizamini byimbaraga za dielectric kugirango babipime kugirango bamenye ububi.Nkigisubizo, sisitemu yo kwipimisha hejuru ya sisitemu yo gupima ingufu za dielectric kugirango yinjize amavuta yangiritse byoroshye.
Mubisanzwe, umwanya uri hagati ya electrode nini yuzuye yuzuye amavuta.Mugihe cyikizamini, voltage iri hagati ya electrode zombi ikomeje kwiyongera, kandi itangazamakuru ryamavuta rifite imbaraga zinyuranye zishobora kwihanganira amashanyarazi menshi yumuriro w'amashanyarazi atandukanye.Uyu muriro uzamuka cyane wumuriro w'amashanyarazi utera itangazamakuru ryamavuta ya insuline kumeneka gitunguranye mugihe ridashobora kwihanganira.Umuyoboro munini ukusanyirizwa hamwe nigikoresho uhita ufunga ugatakaza voltage ndende hanyuma ugahinduka kumanuka.
GD6100D Amavuta yo kubika Tan Delta Ikizamini
Iyo ugerageje amavuta meza adafite amazi aremereye, voltage iri hagati ya electrode yisi yisi ikomeza kwiyongera, kandi mugihe kimwe, ibice byamazi mumavuta ya peteroli byinjira mumyanya iri hagati yimipira ikorwa na a amashanyarazi menshi-yumuriro kugirango akore ibara ryera ryijimye rimeze nkinkingi yamazi.Umubyimba, kurwanya amazi biragenda biba bito.Ubu buryo bwinzibacyuho aho kurwanya amazi bigenda biba bito kandi numuyoboro wa voltage mwinshi wiyongera (utabanje kumeneka no gusohora gitunguranye) bizatera kwangirika kwicyuma, inzitizi igabanya ubukana, fuse izashya, ndetse na transformateur yumuriro mwinshi wigikoresho kizatwikwa.
Ikizamini cyumuvuduko ukabije wamavuta
Ubu bwoko bwamavuta busanzwe buri kuri 15 ~ 35KV.Nubwo amavuta ya peteroli arimo amazi make n’umwanda, igikoresho kirashobora kugerageza bisanzwe.Byerekana gusa ko uduce tumwe na tumwe (cyangwa umwanda) twerekanwe ku cyuho kiri hagati yimipira kugirango habeho gusohora mugihe cyo kongera imbaraga.Ibibyimba byo mu kirere byacitse kandi bivanwa mu cyuho kiri hagati y’imipira, kandi amavuta aruzuzwa, bityo igitutu gikomeza kwiyongera kugeza aho igipimo kinini cy’amavuta kimenetse.Ubu bwoko bwikizamini buracyizewe.
Ikizamini cyamavuta yo hasi
Mugihe cyo kugarura amavuta yo kuyungurura, nkibitonyanga byamazi cyangwa umwanda ushobora kugaragara nijisho ryonyine, nibyiza kudakoresha ingufu kubikoresho byo kwipimisha.Muburyo bwa peteroli ntoya yabitswe mumasaha arenga 24, ibitonyanga binini byamazi bigwa munsi yamavuta, kandi uduce twinshi duto duto tureremba hejuru yamavuta.Umukoresha akeneye gukoresha ibikoresho bitanduye amazi kugirango akuremo urugero rwamavuta mugice cyo hagati.Mugihe cyikizamini, witegereze neza niba hari inkingi yibicu nkurudodo ruto nkuko bigaragara ku gishushanyo cya 9 mugihe umuvuduko wiyongereye (guhera mugihe cyambere cyumuvuduko wiyongera).Zimya amashanyarazi ako kanya kugirango uhagarike ikizamini.Cyangwa niba hari ingingo nyinshi zo gukomeza gusohora mugihe cyo kongera imbaraga, igikoresho ntigishobora guhita gifunga, kandi uyikoresha agomba guhita azimya amashanyarazi agahagarika ikizamini.
Ivangura ryibisubizo
Mu kizamini, spark isohora voltage ihinduka mubihe bine:
(1) Ikirere cya kabiri gisohora voltage ni gito cyane.Agaciro kiki kizamini gishobora kuba gito bitewe ningaruka zimpamvu zimwe zo hanze zizanwa nicyitegererezo cyamavuta mugikombe cyamavuta cyangwa hejuru ya electrode yanduye yikombe cyamavuta mbere yo kuzuza amavuta.Muri iki gihe, impuzandengo yikigereranyo inshuro 2-6 irashobora gufatwa.
.Ni ukubera ko urwego rwubushuhe bwamavuta rutezimbere nyuma yamavuta asohotse.
(3) Umuvuduko wa voltage yibintu bitandatu bisohoka bigenda bigabanuka buhoro buhoro.Mubisanzwe, igaragara mumavuta asukuye yikizamini, kubera ko uduce duto duto twubusa, ibyuka bihumeka hamwe na karubone byiyongera bikurikiranye, byangiza imikorere yamavuta.Byongeye kandi, bamwe bapima amavuta yikora ntibakanguka mugihe cyibizamini 6 bikurikiranye, kandi electrode iri hagati ya electrode Ibice bya karubone bigenda byiyongera buhoro buhoro, bigatuma igabanuka rya gahoro gahoro.
(4) Ikirere gisohora voltage agaciro kari hasi kumpande zombi no hejuru hagati.Nibisanzwe.
Niba hari ikwirakwizwa ryinshi ryumubyigano wa voltage, kurugero: mubizamini 6 byakozwe ukurikije uburyo bwo gukumira ikizamini, agaciro kigihe kimwe gitandukana nizindi ndangagaciro kubwinshi, agaciro kiki gihe ntigashobora kubarwa , cyangwa ikizamini cyicyitegererezo cyamavuta kizongera gufatwa.Birashoboka cyane ko biterwa nubwiza bwamavuta cyangwa gukwirakwiza karubone yubusa.
Bitewe no gukwirakwiza kwinshi kwamavuta kwihanganira ibisubizo byikizamini cya voltage, niba voltage yamenetse ari ndende cyane (hafi ya 80KV) cyangwa ibisubizo ni kimwe buri gihe, bivuze ko igikoresho gishobora kwangirika, nyamuneka hamagara uwagikoze.