GDKC-12A (GDKC-12B) (GDKC-13A) Isesengura ry'umuzunguruko
Umuvuduko mwinshi w'amashanyarazi ni kimwe mubikoresho byingenzi bigenzura sisitemu y'amashanyarazi.GDKC-12A / B (GDKC-13A) ikoreshwa mugupima ibimenyetso biranga imbaraga z'umuvuduko mwinshi w'amashanyarazi.Biroroshye gukora, hamwe nukuri.
●Igihe: gufungura / gufunga igihe, mugice cyo guhuza icyiciro, icyiciro-cy-icyiciro cyo guhuza 12huza.
●Gufunga résistoriste: mbere yo guhinduranya umwanya, mbere yo guhinduranya imirongo ya flim no kurwanya rezo yo gufunga imiyoboro 6.
●Kumenyekanisha: gufunga-gufungura, gufungura-gufunga, gufungura-gufunga igihe kuri buri mubonano.
●Bounce: gufunga igihe, ibihe, inzira hamwe na flake ya buri konti.
●Umuvuduko: umuvuduko kuri contact ufunguye cyangwa ufunze, umuvuduko ntarengwa, igihe-ingendo iranga umurongo;banza ufungure, ubanza gufunga na kabiri gufungura umuvuduko wa reclosure.
●Urugendo: ingendo zose, ingendo zifunguye, hejuru yingendo, kurenza urugero, bounce amplitude.
●Ibiriho: fungura / funga ikigezweho, igishushanyo mbonera cyerekana ifungura / gufunga igiceri.
●Imikorere ya voltage: yubatswe muri DC30 ~ 300V / 20A sisitemu, imbaraga zishobora guhinduka inkomoko ya breaker, ihita yuzuza LV igeragezwa ryibikorwa bya break break hanyuma igapima ibikorwa bya voltage agaciro kumashanyarazi.
●IPC kubakira.
●Birakwiye kugerageza ibipimo byuburyo bwubwoko bwose bwa SF6 yamashanyarazi, GIS ikomatanya ibikoresho byamashanyarazi, icyuma cyumuzunguruko, icyuma cyamavuta.
●Ubushobozi bukomeye bwo kurwanya-kwivanga.Irashobora kandi kugerageza byoroshye no gupima neza na interbus ibaho muri 500kV.
●Hamwe na sensor yumuvuduko rusange (utabishaka), umurongo wumuvuduko wumurongo, sensor rotary, byoroshye gushiraho.
●Igihe kimwe gusa igikorwa cyo kubona amakuru yose hamwe nuburyo bujyanye na breaker ya test ya test.
●Kubika amakuru yikizamini cyamatsinda 1000, yubatswe-mugihe-nyacyo, cyoroshye kubika itariki yikizamini nigihe.
●LCD ya ecran yerekana, hamwe no guhinduranya hamwe no kwibuka-power-off.
●Buit-in printer, kugirango ubone amakuru yose nigishushanyo igihe icyo aricyo cyose byihuse.
●Hamwe na software yameneka yamakuru yo gusesengura software.Irashobora kuvugana na PC.Ibisubizo byikizamini bibitswe mu buryo butaziguye muri disiki ikomeye, kandi birashobora gusohoka muburyo butandukanye bwubwoko bwa inshinge, laser cyangwa inkjet icapiro ryo gucapa raporo yikizamini, kugirango ikizamini cyumurima kuri mudasobwa.
●Koresha U disiki kugirango ubike kandi wohereze amakuru muburyo butaziguye.
●Porogaramu isesenguye ihuye ikusanywa ukurikije ibisobanuro byo gufungura, gufunga umuvuduko.Birakwiriye gupima umuvuduko kubwoko ubwo aribwo bwose bwo guhinduranya.
●Ibidukikije
Imbaraga zinjiza: 220V ± 10%, 50Hz ± 10% / GDKC-12B: 230V ± 10%, 60Hz ± 10%
Umuvuduko w'ikirere: 86-106kpa
Ubushyuhe: -10-40 ℃
Ubushuhe: ≤80% RH
●Imikorere yumutekano
Kurwanya Kurwanya> 2MΩ
Imbaraga za Dielectric: Igikonoshwa gishobora kwihanganira ingufu za voltage 1.5kV kumunota 1 nta flashover na arcing.
●Ibipimo fatizo
a.Igihe: Urwego 20000.0ms gukemura 0.01m
Ikosa 0.1ms ± 1digit muri 2000ms
1ms ± 1digit muri 20000m
GDKC-12B Ibipimo fatizo
a.Igihe: Urwego 20000.0ms gukemura 0.01m
Ikosa 0.01ms ± 2digit muri 250m
0.1ms ± 2digit muri 2500m
1ms ± 2 imibare muri 20000m
GDKC-13A Isesengura ry'umuzengurukoIbipimo fatizo
Igihe: Urwego 4000.0 + 6000.0 ms gukemura 0.1ms
Ikosa 0.1ms ± 1digit muri 100ms
0.1% ± 1igaragaza hejuru ya 100m
Igihe kimwe
b.Umuvuduko: Urwego 20.00m / s gukemura 0.01m / s
Ikosa ± 0.1m / s ± 1digit muri 0-2m / s
± 0.2m / s ± 1digit hejuru ya 2m / s (± 0.2m / s ± 1digit irenga 100m)
c.Urugendo:
Ubwoko | Urwego | Icyemezo | Ikosa |
Kumena icyuho | 50.0mm | 0.1mm | 0.1± 1imibare |
SF6 yameneka | 300.0mm | 1mm | |
Amavutakumena inzitizi | 600.0mm |
d.Ibiriho: intera 20.00A imyanzuro 0.01A
e.Imbaraga zisohoka: DC0-300V ya digitale ishobora guhinduka / 20A (gukora ako kanya), gukemura 1V.
f.Ibipimo: 360mm (L) * 280mm (W) * 300mm (H)
g.Uburemere: 10kg (9kg)
h.GDKC-13A Uburemere: 9kg